High-elevation diesel standby set

A plant runs 180 kW at 0.8 PF and must pick up a 110 kVA motor at 3,200 ft and 95 °F.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

60 Hz · US customaryEdit inputs
Load pickup and fuel consumption at 60 Hz STANDBY KW301.39kWSTANDBY KVA376.74kVASITE CAPACITY88.92%TANK RUNTIME16.65hModeled load stepSite limit 335 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWTank16.7 hSite rating88.9% retained100% rated

Detailed results
Required standby nameplate power
301.39 kW
Required standby nameplate capacity
376.74 kVA
Available capacity factor
88.92%
Elevation derating
9.45%
Temperature derating
1.8%
Pre-step running apparent power
225 kVA
Modeled pickup apparent power
335 kVA
Modeled pickup real power
218.5 kW
Available standby power at site
268 kW
Available standby capacity at site
335 kVA
Running load on nameplate
59.72%
Fuel rate at running load
13.51 gal/h
Fuel rate at 25% of nameplate
7.23 gal/h
Fuel rate at 50% of nameplate
11.75 gal/h
Fuel rate at 75% of nameplate
16.28 gal/h
Fuel rate at 100% of nameplate
21.1 gal/h
Usable diesel volume
225 gal
Estimated diesel runtime
16.65 h

Worked calculation

Compute 180/0.8 + 110 = 335 pickup kVA. Apply both site factors, then use the interpolated diesel rate at running load and 250·0.90 usable gallons for autonomy.

Available capacity factor
88.92%
Required standby nameplate capacity
376.74 kVA
Estimated diesel runtime
16.65 h

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.