Idle before an emergency motor start

An emergency pump is the first load the diesel set sees. It draws 160 kVA in the modeled initial step.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

60 Hz · US customaryEdit inputs
Load pickup and fuel consumption at 60 Hz STANDBY KW128kWSTANDBY KVA160kVASITE CAPACITY100%TANK RUNTIME43.75hModeled load stepSite limit 160 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWTank43.8 hSite rating100% retained100% rated
  • The fuel rate describes modeled idle consumption before the load step.

Detailed results
Required standby nameplate power
128 kW
Required standby nameplate capacity
160 kVA
Available capacity factor
100%
Elevation derating
0%
Temperature derating
0%
Pre-step running apparent power
0 kVA
Modeled pickup apparent power
160 kVA
Modeled pickup real power
44.8 kW
Available standby power at site
128 kW
Available standby capacity at site
160 kVA
Running load on nameplate
0%
Fuel rate at running load
1.28 gal/h
Fuel rate at 25% of nameplate
3.07 gal/h
Fuel rate at 50% of nameplate
4.99 gal/h
Fuel rate at 75% of nameplate
6.91 gal/h
Fuel rate at 100% of nameplate
8.96 gal/h
Usable diesel volume
56 gal
Estimated diesel runtime
43.75 h

Worked calculation

With no pre-step load, size from the 160 kVA pickup and the real-power step. Running fuel consumption at idle uses the 0.010 gal/h per nameplate kW coefficient.

Modeled pickup apparent power
160 kVA
Fuel rate at running load
1.28 gal/h
Estimated diesel runtime
43.75 h

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.