Worked calculation
Compute 180/0.8 + 110 = 335 pickup kVA. Apply both site factors, then use the interpolated diesel rate at running load and 250·0.90 usable gallons for autonomy.
- Available capacity factor
- 88.92%
- Required standby nameplate capacity
- 376.74 kVA
- Estimated diesel runtime
- 16.65 h
Values in this solution use the original example inputs.
Formulas & assumptions
Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.