Diesel set at reference conditions

An industrial booster station at 500 ft and 77 °F carries 96 kW and a 45 kVA step.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

60 Hz · US customaryEdit inputs
Load pickup and fuel consumption at 60 Hz STANDBY KW132kWSTANDBY KVA165kVASITE CAPACITY100%TANK RUNTIME14.68hModeled load stepSite limit 165 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWTank14.7 hSite rating100% retained100% rated

Detailed results
Required standby nameplate power
132 kW
Required standby nameplate capacity
165 kVA
Available capacity factor
100%
Elevation derating
0%
Temperature derating
0%
Pre-step running apparent power
120 kVA
Modeled pickup apparent power
165 kVA
Modeled pickup real power
111.75 kW
Available standby power at site
132 kW
Available standby capacity at site
165 kVA
Running load on nameplate
72.73%
Fuel rate at running load
6.95 gal/h
Fuel rate at 25% of nameplate
3.17 gal/h
Fuel rate at 50% of nameplate
5.15 gal/h
Fuel rate at 75% of nameplate
7.13 gal/h
Fuel rate at 100% of nameplate
9.24 gal/h
Usable diesel volume
102 gal
Estimated diesel runtime
14.68 h

Worked calculation

Both derating losses are zero at the thresholds. The running apparent load is 96/0.8 = 120 kVA, and the preliminary pickup capacity is 165 kVA.

Available capacity factor
100%
Required standby nameplate capacity
165 kVA
Fuel rate at running load
6.95 gal/h

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.

Engineering references

More worked examples