240 V single-phase comparison

A single-phase industrial test load draws 35 A with 240 V across two lines and a lagging PF of 0.90.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.

Power triangle and phase currents

60 Hz · US customaryEdit inputs
Power triangle and phase currents at 60 Hz REAL POWER7.56kWAPPARENT8.4kVAREACTIVE3.66kVARNEUTRAL—Complex powerφ 25.8°P · kWQ · kVARS · kVALine current phasors1φL1Power factor90%1.0 PF

Detailed results
Real power
7.56 kW
Apparent power
8.4 kVA
Signed reactive power
3.66 kVAR
Signed phase angle
25.84°
Line-to-line voltage
240 V
Line-to-neutral voltage
Unavailable
Winding voltage
240 V
Line current
35 A
Winding current
35 A
Neutral RMS current
Unavailable
Single-phase apparent power at equal V & A
8.4 kVA
Single-phase real power at equal V & A
7.56 kW

Worked calculation

Use 240 × 35 / 1000 for kVA. Multiply by 0.90 for kW. For the same numeric line voltage and current, a balanced three-phase load would have √3 times the apparent power.

Apparent power
8.4 kVA
Real power
7.56 kW
Signed phase angle
25.84°

Values in this solution use the original example inputs.

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.