Delta with measured winding amps

A repair shop records 55 A in a winding of a balanced 480 V Delta load at 0.82 PF.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.

Power triangle and phase currents

60 Hz · US customaryEdit inputs
Power triangle and phase currents at 60 Hz REAL POWER64.94kWAPPARENT79.2kVAREACTIVE45.33kVARNEUTRAL—Complex powerφ 34.9°P · kWQ · kVARS · kVALine current phasorsΔL1L2L3Power factor82%1.0 PF

Detailed results
Real power
64.94 kW
Apparent power
79.2 kVA
Signed reactive power
45.33 kVAR
Signed phase angle
34.92°
Line-to-line voltage
480 V
Line-to-neutral voltage
Unavailable
Winding voltage
480 V
Line current
95.26 A
Winding current
55 A
Neutral RMS current
Unavailable
Single-phase apparent power at equal V & A
45.73 kVA
Single-phase real power at equal V & A
37.5 kW

Worked calculation

Voltage across a Delta winding stays at 480 V. The feeder line current is √3 times 55 A. Compute reactive power from the resulting three-phase kVA and sin(acos(0.82)).

Winding voltage
480 V
Line current
95.26 A
Signed reactive power
45.33 kVAR

Values in this solution use the original example inputs.

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.