Uneven Wye phase currents

A 277/480 V, four-wire board supplies 160 A, 112 A and 143 A of fundamental current on L1, L2 and L3.

Inputs

Supply & load
Enter the selected voltage reference. Delta uses line-to-line voltage.
Neutral study

Power triangle and phase currents

60 Hz · US customaryEdit inputs
Power triangle and phase currents at 60 Hz REAL POWER107.08kWAPPARENT116.39kVAREACTIVE45.62kVARNEUTRAL42.15AComplex powerφ 23.1°P · kWQ · kVARS · kVALine current phasorsYL1L2L3N sumNeutral current42.2 A160 A ref.
  • The entered phase currents affect the neutral result and phasors. The power triangle uses the balanced line current.

Detailed results
Real power
107.08 kW
Apparent power
116.39 kVA
Signed reactive power
45.62 kVAR
Signed phase angle
23.07°
Line-to-line voltage
480 V
Line-to-neutral voltage
277.13 V
Winding voltage
277.13 V
Line current
140 A
Winding current
140 A
Neutral RMS current
42.15 A
Single-phase apparent power at equal V & A
67.2 kVA
Single-phase real power at equal V & A
61.82 kW

Worked calculation

Sum the rectangular phasor components 160 − (112 + 143)/2 and √3·(143 − 112)/2. Their hypotenuse gives neutral RMS current. The separate balanced power reference uses 140 A at 0.92 PF.

Neutral RMS current
42.15 A
Line current
140 A
Real power
107.08 kW

Values in this solution use the original example inputs.

Formulas & assumptions

Apparent, real and reactive power

S = √3 · V_LL · I_L / 1000, P = S · PF, Q = S · sin φ

For a balanced three-phase load, use RMS line quantities. For single-phase, replace √3 with 1 and use the applied voltage. φ = acos(PF) for lagging current and −acos(PF) for leading current.

Wye and Delta winding quantities

Y: V_w = V_LL / √3, I_w = I_L. Δ: V_w = V_LL, I_w = I_L / √3.

In four-wire Wye, winding voltage equals line-to-neutral voltage. The balanced Delta model has three wires and no line-to-neutral output. For single-phase, choose line-to-line or line-to-neutral according to the two supply terminals.

Optional Wye neutral vector

I_N = |I_A + I_B∠−120° + I_C∠+120°|

The neutral magnitude uses three fundamental RMS currents spaced 120° apart with the same displacement angle. The balanced power calculation is independent of these entries. Harmonic neutral loading uses the harmonic calculator.

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.