ACI 318-19 §7.3 / §7.6 / §24.4

Cantilever strip with top flexural steel

A 7 ft projection carries a factored strip moment at its fixed end.

Edit inputs ↓

Inputs

Editable example

Slab & demand
Bar layout
φMn / strip 15.89kip·ft/ft
Thickness min 8.4in
Steel min 0.194in²/ft
Flex spacing 18in
AnatomyDiagrammatic scale
Parameter-linked slab drawing. Diagrammatic scale. CANTILEVERhℓ 7 ftd 7.94 ins 8 in

Screening

Within screening limits
Strip moment utilization69.2%
Tension controlled30.8% below the threshold
  • Flexural strengthMu ≤ φMn for the design strip
    Within limit
  • Tension controlεt ≥ εty + 0.003 per §7.3.3.1
    Within limit
  • Minimum strip reinforcementFlexural and transverse T&S steel each ≥ 0.0018Ag
    Within limit
  • Minimum clear bar spacingClear spacing ≥ max(1 in, db); check aggregate size separately
    Within limit
  • Maximum bar spacingFlexural and T&S bar spacing within upper limits
    Within limit
  • Minimum thicknessh meets the span-to-depth shortcut
    Within limit

Normalweight, solid nonprestressed slabs. The thickness shortcut assumes no damage-sensitive attachments. Check load combinations, one-way shear, anchorage and the crack-control spacing of §24.3 separately.

Calculation readout
QuantityValue
Strip design moment φMn15.89 kip·ft/ft
Minimum slab thickness8.4 in
ACI minimum strip steel0.194 in²/ft
Maximum flexural spacing18 in
Effective depth d7.938 in
Provided flexural steel0.465 in²/ft
Provided transverse T&S steel0.31 in²/ft
Maximum T&S spacing18 in
Grade-scaled reference (legacy)0.194 in²/ft
Net tensile strain εt26,599 με
Strength factor φ0.9

Original example

Worked solution

Default calculator ↗

Starting inputs

Clear span ℓ
7 ft
Support condition
Cantilever
Slab thickness h
9 in
Factored strip moment Mu
11 kip·ft/ft
Flexural bar spacing
8 in
Transverse bar size
#5

Calculated result

Strip design moment φMn
15.89 kip·ft/ft
Minimum slab thickness
8.4 in
ACI minimum strip steel
0.194 in²/ft
Maximum flexural spacing
18 in

Use ℓ/10 and measure effective depth from the compression face. On this cantilever, tension is at the top.

Preset screening · Tension controlled · Within limits

How the check works

Code basis ↗
  1. Apply ℓ/20, ℓ/24, ℓ/28 or ℓ/10 and the factor (0.4 + fy/100,000). A thinner slab requires a calculated deflection check.
  2. Find d from h, clear cover and half of the bar diameter. Calculate Aₛ per unit width and the tension-controlled φMn using the same strain-compatible rectangular block as the beam tool.
  3. ACI 318-19 §§7.6.1.1 and 24.4.3.2 use 0.0018Ag for flexure and deformed T&S steel. Use the ACI 318-19 minimum for screening. Check upper spacing of min(3h, 18 in) for flexure and min(5h, 18 in) for T&S. Clear spacing must also reach max(1 in, db); verify the aggregate-size term separately.