ACI 318-19 §8.7 / §22.6

Corner reaction above punching capacity

Two free edges shorten the critical perimeter under factored direct shear.

Edit inputs ↓

Inputs

Editable example

Reaction & slab
Shear reinforcement
Perimeter bo 43in
Baseline φVc 57.11kip
φVn 57.11kip
Size λs 1 
AnatomyDiagrammatic scale
Parameter-linked punching drawing. Diagrammatic scale. CORNER COLUMN PLANCritical linec₁ 18 ind/2 3.5 inbo 43 in

Screening

Limit exceeded
Punching utilization148.8%
(a) basic stress48.8% over the threshold
  • Concrete punching strengthVu ≤ φVc at the inner perimeter
    Outside limit

Direct shear only. Supply net Vu at the section. Check unbalanced moment, openings, slab edge offsets, the actual perimeter geometry and local slab flexural steel per §8.6.1.2. For studs, provide the shortest enclosing outer perimeter and verify head, rail and cover detailing.

Calculation readout
QuantityValue
Inner critical perimeter bo43 in
Unreinforced strength φVc57.11 kip
Governing design shear φVn57.11 kip
Size effect factor λs1
Inner demand stress vu282.39 psi
Column aspect ratio βc1
Position factor αs20
Concrete stress eq. (a)252.98 psi
Concrete stress eq. (b)379.47 psi
Concrete stress eq. (c)332.41 psi

Original example

Worked solution

Default calculator ↗

Starting inputs

Column position
Corner
Column dimension c₁
18 in
Column dimension c₂
18 in
Average effective depth d
7 in
Factored direct shear Vu
85 kip

Calculated result

Inner critical perimeter bo
43 in
Unreinforced strength φVc
57.11 kip
Governing design shear φVn
57.11 kip
Size effect factor λs
1

At the corner, count only the remaining two perimeter legs. Compare the reduced strength with the corner demand.

Preset screening · (a) basic stress · Limit exceeded

How the check works

Code basis ↗
  1. Measure bo at d/2 with the column faces flush at modeled free edges. Use the lesser of the three stress equations in Table 22.6.5.2, with βc = long side/short side, αs = 40/30/20 and √f′c limited to 100.
  2. For headed studs, use Table 22.6.6.1 for inner concrete stress and add Vs = Av fyt d/s. Use the actual √f′c for the Table 22.6.6.3 inner ceiling and Table 8.7.7.1.2 spacing threshold. Apply the 100 psi root cap to concrete stress, including 2λsλ√f′c at the supplied outer perimeter.
  3. Apply the full entered net shear to both sections as a conservative outer-perimeter screen. Check Av/s ≥ 2√f′c bo/fyt with actual √f′c per §22.6.8.3 and check the first-row, radial and tangential spacing limits.