ACI 318-19 §8.7 / §22.6

Headed studs with an outer perimeter check

A regular stud layout extends the available punching resistance, subject to the outer control section.

Edit inputs ↓

Inputs

Editable example

Reaction & slab
Shear reinforcement
Perimeter bo 106in
Baseline φVc 150.84kip
φVn 126.65kip
Size λs 1 
AnatomyDiagrammatic scale
Parameter-linked punching drawing. Diagrammatic scale. INTERIOR COLUMN PLANCritical linec₁ 18 ind/2 3.75 inbo 106 in

Screening

Within screening limits
Punching utilization98.7%
Studs · outer governs1.3% below the threshold
  • Inner punching strengthVu ≤ inner φ(Vc + Vs) and the stress ceiling
    Within limit
  • Outer punching strengthCheck full entered Vu at the outer perimeter
    Within limit
  • Minimum headed stud areaAv/s ≥ 2√f′c bo/fyt
    Within limit
  • Stud layout spacingFirst row ≤ d/2, radial spacing ≤ smax and along-row spacing ≤ 2d
    Within limit

Direct shear only. Supply net Vu at the section. Check unbalanced moment, openings, slab edge offsets, the actual perimeter geometry and local slab flexural steel per §8.6.1.2. For studs, provide the shortest enclosing outer perimeter and verify head, rail and cover detailing.

Calculation readout
QuantityValue
Inner critical perimeter bo106 in
Unreinforced strength φVc150.84 kip
Governing design shear φVn126.65 kip
Size effect factor λs1
Inner demand stress vu157.23 psi
Column aspect ratio βc1.11
Position factor αs40
Concrete stress eq. (a)252.98 psi
Concrete stress eq. (b)354.18 psi
Concrete stress eq. (c)305.49 psi
Concrete with studs φVc113.13 kip
Stud shear contribution Vs135 kip
Inner design shear φVn214.38 kip
Outer design shear φVc126.65 kip
Minimum stud area rate Av/s0.2235 in²/in
Maximum stud row spacing5.63 in

Original example

Worked solution

Default calculator ↗

Starting inputs

Factored direct shear Vu
125 kip
Punching reinforcement
Headed studs
Outer critical perimeter bo
178 in

Calculated result

Inner critical perimeter bo
106 in
Unreinforced strength φVc
150.84 kip
Governing design shear φVn
126.65 kip
Size effect factor λs
1

Check the stud-reinforced inner section and the concrete-only outer section, where the full entered shear is kept for screening.

Preset screening · Studs · outer governs · Within limits

How the check works

Code basis ↗
  1. Measure bo at d/2 with the column faces flush at modeled free edges. Use the lesser of the three stress equations in Table 22.6.5.2, with βc = long side/short side, αs = 40/30/20 and √f′c limited to 100.
  2. For headed studs, use Table 22.6.6.1 for inner concrete stress and add Vs = Av fyt d/s. Use the actual √f′c for the Table 22.6.6.3 inner ceiling and Table 8.7.7.1.2 spacing threshold. Apply the 100 psi root cap to concrete stress, including 2λsλ√f′c at the supplied outer perimeter.
  3. Apply the full entered net shear to both sections as a conservative outer-perimeter screen. Check Av/s ≥ 2√f′c bo/fyt with actual √f′c per §22.6.8.3 and check the first-row, radial and tangential spacing limits.