Concrete punching strengthVu ≤ φVc at the inner perimeter
Within limit
Direct shear only. Supply net Vu at the section. Check unbalanced moment, openings, slab edge offsets, the actual perimeter geometry and local slab flexural steel per §8.6.1.2. For studs, provide the shortest enclosing outer perimeter and verify head, rail and cover detailing.
Measure bo at d/2 with the column faces flush at modeled free edges. Use the lesser of the three stress equations in Table 22.6.5.2, with βc = long side/short side, αs = 40/30/20 and √f′c limited to 100.
For headed studs, use Table 22.6.6.1 for inner concrete stress and add Vs = Av fyt d/s. Use the actual √f′c for the Table 22.6.6.3 inner ceiling and Table 8.7.7.1.2 spacing threshold. Apply the 100 psi root cap to concrete stress, including 2λsλ√f′c at the supplied outer perimeter.
Apply the full entered net shear to both sections as a conservative outer-perimeter screen. Check Av/s ≥ 2√f′c bo/fyt with actual √f′c per §22.6.8.3 and check the first-row, radial and tangential spacing limits.
Direct two-way shear · d/2 perimeter · Within screening limits
Inputs
Column position
Interior
Column dimension c₁
609.6 mm
Column dimension c₂
609.6 mm
Average effective depth d
457.2 mm
Concrete strength f′c
41.369 MPa
Lightweight factor λ
1
Factored direct shear Vu
2,090.664 kN
Punching reinforcement
Without shear reinforcement
Calculated values
Inner critical perimeter bo
4,267.2 mm
Unreinforced strength φVc
2,641.81 kN
Governing design shear φVn
2,641.81 kN
Size effect factor λs
0.845
Inner demand stress vu
1.07 MPa
Column aspect ratio βc
1
Position factor αs
40
Concrete stress eq. (a)
1.81 MPa
Concrete stress eq. (b)
2.71 MPa
Concrete stress eq. (c)
2.84 MPa
Screening
(a) basic stress · Punching utilization 79.1%
Concrete punching strength · Within limit
Direct shear only. Supply net Vu at the section. Check unbalanced moment, openings, slab edge offsets, the actual perimeter geometry and local slab flexural steel per §8.6.1.2. For studs, provide the shortest enclosing outer perimeter and verify head, rail and cover detailing.