ACI 318-19 §8.7 / §22.6

Thick footing with reduced size factor

The footing has 18 in effective depth and a net punching demand after accounting for support reactions.

Edit inputs ↓

Inputs

Editable example

Reaction & slab
Shear reinforcement
Perimeter bo 4,267.2mm
Baseline φVc 2,641.81kN
φVn 2,641.81kN
Size λs 0.845 
AnatomyDiagrammatic scale
Parameter-linked punching drawing. Diagrammatic scale. INTERIOR COLUMN PLANCritical linec₁ 609.6 mmd/2 228.6 mmbo 4,267.2 mm

Screening

Within screening limits
Punching utilization79.1%
(a) basic stress20.9% below the threshold
  • Concrete punching strengthVu ≤ φVc at the inner perimeter
    Within limit

Direct shear only. Supply net Vu at the section. Check unbalanced moment, openings, slab edge offsets, the actual perimeter geometry and local slab flexural steel per §8.6.1.2. For studs, provide the shortest enclosing outer perimeter and verify head, rail and cover detailing.

Calculation readout
QuantityValue
Inner critical perimeter bo4,267.2 mm
Unreinforced strength φVc2,641.81 kN
Governing design shear φVn2,641.81 kN
Size effect factor λs0.845
Inner demand stress vu1.07 MPa
Column aspect ratio βc1
Position factor αs40
Concrete stress eq. (a)1.81 MPa
Concrete stress eq. (b)2.71 MPa
Concrete stress eq. (c)2.84 MPa

Original example

Worked solution

Default calculator ↗

Starting inputs

Column dimension c₁
609.6 mm
Column dimension c₂
609.6 mm
Average effective depth d
457.2 mm
Concrete strength f′c
41.369 MPa
Factored direct shear Vu
2,090.664 kN

Calculated result

Inner critical perimeter bo
4,267.2 mm
Unreinforced strength φVc
2,641.81 kN
Governing design shear φVn
2,641.81 kN
Size effect factor λs
0.845

The depth increases shear area while reducing λs. Enter only the net force crossing the critical section.

Preset screening · (a) basic stress · Within limits

How the check works

Code basis ↗
  1. Measure bo at d/2 with the column faces flush at modeled free edges. Use the lesser of the three stress equations in Table 22.6.5.2, with βc = long side/short side, αs = 40/30/20 and √f′c limited to 100.
  2. For headed studs, use Table 22.6.6.1 for inner concrete stress and add Vs = Av fyt d/s. Use the actual √f′c for the Table 22.6.6.3 inner ceiling and Table 8.7.7.1.2 spacing threshold. Apply the 100 psi root cap to concrete stress, including 2λsλ√f′c at the supplied outer perimeter.
  3. Apply the full entered net shear to both sections as a conservative outer-perimeter screen. Check Av/s ≥ 2√f′c bo/fyt with actual √f′c per §22.6.8.3 and check the first-row, radial and tangential spacing limits.