ACI 318-19 §9.3 / §9.6 / §22.2

Wide beam below minimum steel

An 18 in web has enough design moment for the load, but its reinforcement falls below the beam minimum.

Edit inputs ↓

Inputs

Editable example

Section
Reinforcement & demand
φMn 78.73kip·ft
Block a 0.83in
Axis c 0.98in
Strain εt 61,260με
AnatomyDiagrammatic scale
Parameter-linked flexure drawing. Diagrammatic scale. RC SECTIONSTRAINWHITNEY BLOCKhb 18 ind 21 ina 0.83 in

Screening

Limit exceeded
Moment utilization79.4%
Tension controlled20.6% below the threshold
  • Bending strengthMu ≤ φMn
    Within limit
  • Minimum tension steelAs ≥ As,min per §9.6.1.2
    Outside limit
  • Tension controlεt ≥ εty + 0.003 per §9.3.3.1
    Within limit

Positive pure bending of a nonprestressed rectangular beam. The calculation excludes combined axial force, shear, anchorage and the minimum-steel exception in §9.6.1.3.

Calculation readout
QuantityValue
Design moment φMn78.73 kip·ft
Stress block depth a0.83 in
Neutral axis depth c0.98 in
Net tensile strain εt61,260 με
Strength factor φ0.9
Whitney factor β₁0.85
Tension-controlled limit5,069 με
Nominal moment Mn87.48 kip·ft
Minimum tension steel As,min1.26 in²
Concrete compression Cc51 kip
Top steel force Cs,net0 kip
Tension steel force Ts51 kip

Original example

Worked solution

Default calculator ↗

Starting inputs

Section width b
18 in
Tension steel depth d
21 in
Tension steel As
0.85 in²
Factored moment Mu
62.5 kip·ft

Calculated result

Design moment φMn
78.73 kip·ft
Stress block depth a
0.83 in
Neutral axis depth c
0.98 in
Net tensile strain εt
61,260 με

Compare the minimum steel check with the demand ratio. Low utilization alone does not satisfy the reinforcement provision.

Preset screening · Tension controlled · Limit exceeded

How the check works

Code basis ↗
  1. β₁ drops linearly from 0.85 at 4,000 psi by 0.05 per additional 1,000 psi, with a 0.65 floor at 8,000 psi. The two strength thresholds display as approximately 27.6 and 55.2 MPa.
  2. Solve force equilibrium using εcu = 0.003, a = β₁c and elastic-perfectly plastic steel. Deduct 0.85f′c from the stress of top steel inside the concrete block. Sum moments of the compression forces about the tension steel.
  3. Use φ = 0.65 below εty and interpolate to 0.90 at εty + 0.003, with εty = fy/Es. Check tension control and As,min = max(3√f′c, 200)bw d / min(fy, 80 ksi).