Minimum strip reinforcementFlexural and transverse T&S steel each ≥ 0.0018Ag
Within limit
Minimum clear bar spacingClear spacing ≥ max(1 in, db); check aggregate size separately
Within limit
Maximum bar spacingFlexural and T&S bar spacing within upper limits
Within limit
Minimum thicknessh meets the span-to-depth shortcut
Within limit
Normalweight, solid nonprestressed slabs. The thickness shortcut assumes no damage-sensitive attachments. Check load combinations, one-way shear, anchorage and the crack-control spacing of §24.3 separately.
Apply ℓ/20, ℓ/24, ℓ/28 or ℓ/10 and the factor (0.4 + fy/100,000). A thinner slab requires a calculated deflection check.
Find d from h, clear cover and half of the bar diameter. Calculate Aₛ per unit width and the tension-controlled φMn using the same strain-compatible rectangular block as the beam tool.
ACI 318-19 §§7.6.1.1 and 24.4.3.2 use 0.0018Ag for flexure and deformed T&S steel. Use the ACI 318-19 minimum for screening. Check upper spacing of min(3h, 18 in) for flexure and min(5h, 18 in) for T&S. Clear spacing must also reach max(1 in, db); verify the aggregate-size term separately.
Solid slab · unit-width strip · Within screening limits
Inputs
Clear span ℓ
12 ft
Support condition
Simply supported
Slab thickness h
8 in
Clear flexural cover
0.75 in
Concrete strength f′c
4,000 psi
Steel yield strength fy
60 ksi
Factored strip moment Mu
7 kip·ft/ft
Flexural bar size
#5
Flexural bar spacing
10 in
Transverse bar size
#4
T&S bar spacing
12 in
Calculated values
Strip design moment φMn
11.16 kip·ft/ft
Minimum slab thickness
7.2 in
ACI minimum strip steel
0.173 in²/ft
Maximum flexural spacing
18 in
Effective depth d
6.938 in
Provided flexural steel
0.372 in²/ft
Provided transverse T&S steel
0.2 in²/ft
Maximum T&S spacing
18 in
Grade-scaled reference (legacy)
0.173 in²/ft
Net tensile strain εt
29,338 με
Strength factor φ
0.9
Screening
Tension controlled · Strip moment utilization 62.7%
Flexural strength · Within limit
Tension control · Within limit
Minimum strip reinforcement · Within limit
Minimum clear bar spacing · Within limit
Maximum bar spacing · Within limit
Minimum thickness · Within limit
Normalweight, solid nonprestressed slabs. The thickness shortcut assumes no damage-sensitive attachments. Check load combinations, one-way shear, anchorage and the crack-control spacing of §24.3 separately.