RoomAcousticLab · Calculation record
Partition transmission example
Clinic room door undercut
A 10-millimetre by 0.9-metre opening is modelled as a fully open slit. Compare its leak area with the sealed-door case.
Inputs
- Composite TL
- 32.6dB
- Wall penalty
- 20.39dB
- Open gap
- 0.0529%
- Target margin
- -10.39dB
Partition elevation & leak response
Illustrative scaleTransmission target shortfall
LimitThe modelled value falls on the wrong side of the entered target.
≥ 3 dB reserve0–3 dB reserveBelow target
Input snapshot
- Total area
- 17 m²
- Solid wall TL
- 53 dB
- Target TL
- 43 dB
- Weak element
- Door
- Element area
- 2 m²
- Element TL
- 39 dB
- Open gap area
- 0.009 m²
Calculation breakdown
- Solid wall area
- 14.99 m²
- Weak element share
- 11.765%
- Transmission loss with the gap sealed
- 47.16 dB
- Target band TL
- 43 dB
| Open area | Composite TL | Wall penalty |
|---|---|---|
| 0% | 47.16 dB | 5.84 dB |
| 0.001% | 45.34 dB | 7.659 dB |
| 0.01% | 39.24 dB | 13.764 dB |
| 0.05294% | 32.61 dB | 20.393 dB |
| 0.1% | 29.92 dB | 23.083 dB |
| 1% | 19.99 dB | 33.008 dB |
| 5% | 13.01 dB | 39.991 dB |
Matched single-number ratings can provide a rough comparison. A rated composite STC requires a frequency-band TL curve and the ASTM E413 fitting procedure. Treat indirect structure-borne and duct transmission as separate paths.