RoomAcousticLab · Calculation record
Outdoor noise setback example
Two heat pumps near a wall
Two identical incoherent units share an estimated propagation path. Compare their combined level against the property-line limit.
Inputs
- Receiver SPL
- 63.2dB
- Setback
- 28.3m
- Air loss
- 0dB
- Limit margin
- -8.21dB
Source geometry & receiver setback
Illustrative scaleProperty-line limit exceeded
LimitThe modelled value falls on the wrong side of the entered target.
≥ 3 dB reserve0–3 dB reserveOver limit
Input snapshot
- Source type
- Point source
- Sound power Lw
- 86 dB
- Directivity Q
- 4 · Quarter space
- Identical sources
- 2
- Source addition
- Incoherent · energy
- Receiver distance
- 11 m
- Air attenuation
- 0 dB/km
- Property-line limit
- 55 dB
Calculation breakdown
- Geometrical spreading loss
- 31.82 dB
- Directivity gain
- 6.02 dB
- Identical-source addition
- 3.01 dB
- Entered property-line limit
- 55 dB
- Setback search result
- Solved inside model range
Setback is solved between 0.1 m and 100 km. This model considers divergence and the entered air loss. A site study can include ground impedance, shielding, weather, reflections, background and source spectra as required by the governing method.