Worked example · ASCE/SEI 7-16 §§13.3.1, 13.4 and Chapter 2

Flexible roof equipment at the upper bound

A flexible item has a low component response factor and high importance. The unbounded horizontal force reaches the maximum limit.

Calculation sheet
Export

Inputs

Component and attachment
g
ft
ft
Anchor group geometry
kip
ft
ft
Anchorage overstrength
Anchorage demand

Use 1 unless the attachment provision requires a higher factor.

LATERAL Fₚ
5.914kip
VERTICAL |Eᵥ|
0.493kip
LRFD UPLIFT
7.61kip
ASD UPLIFT
5.369kip

Attachment in elevationComponent attachmentz/h 1h 80 ftSkid free-body diagramAnchor row spacing↑ |Eᵥ| 0.49 kipFₚ 5.91 kipCG 3.5 ftUplift 7.61 kip
The elevation locates the component relative to the roof. The free-body sketch shows the horizontal force and vertical load path.

Calculation detail

Height ratio z/h
1
Unbounded Fₚ
11.088 kip
Minimum Fₚ
1.109 kip
Maximum Fₚ
5.914 kip
Governing Fₚ
Upper bound
Unfactored overturning
20.698 kip·ft
LRFD gravity stability factor
0.118
LRFD support contact
Uplift
ASD gravity stability factor
0.111
ASD support contact
Uplift
Demand on the two anchor rows
Load combinationNet gravity (kip)Uplift row (kip)Opposite row (kip)Shear / row (kip)
LRFD uplift2.02727.610402.9568
ASD uplift1.3355.369302.0698

How the calculation works

Read this example

Compare the displayed unbounded force to the selected maximum before estimating overturning.

Preset result: LATERAL Fₚ 5.914 kip.

Calculate the horizontal force

Eq. 13.3-1 uses 0.4aₚSᴅₛWₚ(Iₚ/Rₚ)(1 + 2z/h). The result is bounded by 0.3SᴅₛIₚWₚ and 1.6SᴅₛIₚWₚ. The attachment-height ratio is at most 1.

Combine overturning and upward vertical action

The worksheet takes |Eᵥ| = 0.2SᴅₛWₚ. The simplified LRFD uplift case is 0.9D − Eᵥ + Eₕ. The ASD case is 0.6D − 0.7Eᵥ + 0.7Eₕ. A selectable horizontal multiplier is applied to the anchorage demand.

Resolve the anchor rows

For a centered component and rigid base, each row takes half the horizontal shear. The tension-side reaction is M divided by row spacing minus half the effective gravity. The gravity stability factor divides the stabilizing gravity moment by the overturning moment. A factor of 1 places the uplift row at the contact limit.

Design scope

Demand screening for a centered equipment skid on two symmetric anchor rows. Verify component classifications, governing combinations, attachment overstrength, capacities, interaction, eccentricity and prying separately.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf