Worked example · ASCE/SEI 7-16 §§13.3.1, 13.4 and Chapter 2
Equipment above the entered roof datum
An elevated roof platform puts the entered attachment height above the roof reference. This preset makes the height cap visible.
Calculation sheet
Export
Inputs
LATERAL Fₚ
5.897kip
VERTICAL |Eᵥ|
0.655kip
LRFD UPLIFT
4.553kip
ASD UPLIFT
3.25kip
Attachment height exceeds roof height
The force calculation caps z/h at 1. Verify the reference height and the support location.
The elevation locates the component relative to the roof. The free-body sketch shows the horizontal force and vertical load path.
Calculation detail
Height ratio z/h
1
Unbounded Fₚ
5.897 kip
Minimum Fₚ
1.474 kip
Maximum Fₚ
7.862 kip
Governing Fₚ
Calculated Fₚ
Unfactored overturning
16.511 kip·ft
LRFD gravity stability factor
0.255
LRFD support contact
Uplift
ASD gravity stability factor
0.241
ASD support contact
Uplift
Demand on the two anchor rows
Load combination
Net gravity (kip)
Uplift row (kip)
Opposite row (kip)
Shear / row (kip)
LRFD uplift
Net gravity (kip)3.1248
Uplift row (kip)4.5528
Opposite row (kip)0
Shear / row (kip)2.9484
ASD uplift
Net gravity (kip)2.0614
Uplift row (kip)3.25
Opposite row (kip)0
Shear / row (kip)2.0639
How the calculation works
Read this example
The equation uses z/h = 1. Confirm whether the platform or main roof is the appropriate reference.
Preset result: LATERAL Fₚ 5.897 kip.
Calculate the horizontal force
Eq. 13.3-1 uses 0.4aₚSᴅₛWₚ(Iₚ/Rₚ)(1 + 2z/h). The result is bounded by 0.3SᴅₛIₚWₚ and 1.6SᴅₛIₚWₚ. The attachment-height ratio is at most 1.
Combine overturning and upward vertical action
The worksheet takes |Eᵥ| = 0.2SᴅₛWₚ. The simplified LRFD uplift case is 0.9D − Eᵥ + Eₕ. The ASD case is 0.6D − 0.7Eᵥ + 0.7Eₕ. A selectable horizontal multiplier is applied to the anchorage demand.
Resolve the anchor rows
For a centered component and rigid base, each row takes half the horizontal shear. The tension-side reaction is M divided by row spacing minus half the effective gravity. The gravity stability factor divides the stabilizing gravity moment by the overturning moment. A factor of 1 places the uplift row at the contact limit.
Design scope
Demand screening for a centered equipment skid on two symmetric anchor rows. Verify component classifications, governing combinations, attachment overstrength, capacities, interaction, eccentricity and prying separately.