Worked example · ASCE/SEI 7-16 §§13.3.1, 13.4 and Chapter 2

Rooftop air-handler skid

A flexible air handler near the roof receives the full height multiplier. A tall center of mass makes the uplift-side anchor row govern.

Calculation sheet
Export

Inputs

Component and attachment
g
ft
ft
Anchor group geometry
kip
ft
ft
Anchorage overstrength
Anchorage demand

Use 1 unless the attachment provision requires a higher factor.

LATERAL Fₚ
15.048kip
VERTICAL |Eᵥ|
1.672kip
LRFD UPLIFT
14.136kip
ASD UPLIFT
10.009kip

Attachment in elevationComponent attachmentz/h 1h 52 ftSkid free-body diagramAnchor row spacing↑ |Eᵥ| 1.67 kipFₚ 15.05 kipCG 4 ftUplift 14.14 kip
The elevation locates the component relative to the roof. The free-body sketch shows the horizontal force and vertical load path.

Calculation detail

Height ratio z/h
1
Unbounded Fₚ
15.048 kip
Minimum Fₚ
3.762 kip
Maximum Fₚ
20.064 kip
Governing Fₚ
Calculated Fₚ
Unfactored overturning
60.192 kip·ft
LRFD gravity stability factor
0.155
LRFD support contact
Uplift
ASD gravity stability factor
0.145
ASD support contact
Uplift
Demand on the two anchor rows
Load combinationNet gravity (kip)Uplift row (kip)Opposite row (kip)Shear / row (kip)
LRFD uplift5.16814.13607.524
ASD uplift3.389610.009205.2668

How the calculation works

Read this example

Anchor row spacing changes overturning demand while the component design force stays fixed.

Preset result: LATERAL Fₚ 15.048 kip.

Calculate the horizontal force

Eq. 13.3-1 uses 0.4aₚSᴅₛWₚ(Iₚ/Rₚ)(1 + 2z/h). The result is bounded by 0.3SᴅₛIₚWₚ and 1.6SᴅₛIₚWₚ. The attachment-height ratio is at most 1.

Combine overturning and upward vertical action

The worksheet takes |Eᵥ| = 0.2SᴅₛWₚ. The simplified LRFD uplift case is 0.9D − Eᵥ + Eₕ. The ASD case is 0.6D − 0.7Eᵥ + 0.7Eₕ. A selectable horizontal multiplier is applied to the anchorage demand.

Resolve the anchor rows

For a centered component and rigid base, each row takes half the horizontal shear. The tension-side reaction is M divided by row spacing minus half the effective gravity. The gravity stability factor divides the stabilizing gravity moment by the overturning moment. A factor of 1 places the uplift row at the contact limit.

Design scope

Demand screening for a centered equipment skid on two symmetric anchor rows. Verify component classifications, governing combinations, attachment overstrength, capacities, interaction, eccentricity and prying separately.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf

More component force & anchors examples