Hot pressurized return into a 5 psig vessel

A pressurized return supplies condensate above the vessel saturation temperature. Cold make-up is mixed with the hot return in the unit.

Inputs

lb/hr
°F
lb/hr
°F
psig
5–15 psig, equivalent to 0.345–1.034 bar g.
psig
%
%
Tray deaerator mass and enthalpy balance
Tray deaerator mass and enthalpy balancePEGGING 1,121.3 lb/hr. FEEDWATER 14.75K lb/hr. SAT TEMP 227.1 °F. FIRING RELIEF 1.299 MMBtu/hPEGGING1,121.3lb/hrFEEDWATER14.75Klb/hrSAT TEMP227.1°FFIRING RELIEF1.299MMBtu/hDEAERATOR TRAYSMAKE-UP WATERCONDENSATEVENT VAPORPEGGING STEAMFEEDWATER OUTPegging steam / external inlet mass8.2%0%Inlet heating burden25% scale
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Mixed inlet temperature
148.62°F
Deaerator saturation temperature
227.1°F
Pegging steam required
1,121.3lb/hr
Liquid feedwater outlet
14,753.1lb/hr
Saturated vent vapor
36.9lb/hr
Net boiler fuel-input relief
1.299MMBtu/h
Preheat credit vs all-cold baseline
2,177,282.3Btu/h
Boiler duty to generate pegging steam
1,112,358.35Btu/h
Mixed inlet enthalpy
116.63Btu/lb
Pegging inlet enthalpy
1,187.44Btu/lb
Feedwater outlet enthalpy
195.42Btu/lb
Vent vapor enthalpy
1,155.9Btu/lb

Check the original case

The return enthalpy enters the balance before throttling. Compare pegging demand with cooler condensate return.

  • Pegging steam required1,121.3 lb/hr
  • Liquid feedwater outlet14,753.1 lb/hr
  • Deaerator saturation temperature227.1 °F
  • Net boiler fuel-input relief1.299 MMBtu/h

Formulas and assumptions

Mixed inlet

h_mix = (m_make·h_make + m_return·h_return)/(m_make + m_return)

The dry supply steam throttles at constant enthalpy. The liquid mix temperature is found by inverting the liquid enthalpy equation.

Mass and energy

h* = (h_f + r·h_g)/(1 + r); m_peg = m_in·(h* − h_mix)/(h_supply − h*)

The vent is r times liquid outlet mass, and the outlet is (m_in + m_peg)/(1 + r). Vent and liquid exit as saturated phases at the deaerator pressure. The energy and mass balances assume steady state and no shell loss.

Fuel-input relief

Net = [m_in·(h_f − h_make) − m_peg·(h_supply − h_f)]/η

Compare at equal external water inflow against an all-cold baseline. The credit includes hot return and subtracts the boiler duty required for pegging. Use site venting and dissolved oxygen requirements for commissioning.