Near-saturation vented steam coil
A vented exchanger condenses at atmospheric pressure while heating process water to 96 °C.
Inputs
Inputs
- Heating mode
- Continuous
- Process fluid flow
- 7,054.8 lb/hr
- Process fluid heat capacity
- 1 Btu/(lb·°F)
- Inlet or initial temperature
- 59 °F
- Outlet or target temperature
- 204.8 °F
- Heat loss margin
- 15 %
- Valve inlet pressure P₁
- 35 psig
- Condensing pressure P₂
- 0 psig
Calculation results
- Small terminal temperature approach. Verify heat-transfer area and available differential pressure.
- Design heating duty
- 1,182,651.02Btu/h
- Process heating duty
- 1,028,392.19Btu/h
- Condensing steam demand
- 1,219.1lb/hr
- Screened trap capacity
- 2,438.1lb/hr
- Trap capacity factor
- 2×
- Required valve Cv
- 15.55Cv
- Required valve Kv
- 13.45Kv
- Valve flow regime
- Choked
- Valve P₂/P₁ absolute
- 29.57%
- Condensing temperature
- 211.95°F
- Steam latent heat
- 970.14Btu/lb
- Terminal temperature approach
- 7.15°F
Calculation basis
- Continuous or batch heat duty
Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes - Steam and trap load
m_steam = Q/h_fg(P₂); m_trap = factor·m_steam - Globe valve coefficient
X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv
Check the original case
Review the small terminal temperature approach. Steam demand alone does not establish the exchanger area.
- Condensing steam demand1,219.1 lb/hr
- Design heating duty1,182,651.02 Btu/h
- Required valve Cv15.55 Cv
- Screened trap capacity2,438.1 lb/hr
Formulas and assumptions
Continuous or batch heat duty
Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes
Use mass per hour for continuous operation or an equivalent hourly batch rate. The target temperature must stay below steam saturation in the exchanger.
Steam and trap load
m_steam = Q/h_fg(P₂); m_trap = factor·m_steam
Use 2× for a continuous screen and 3× for a batch startup screen. Confirm trap capacity at the minimum differential pressure and review exchanger stall.
Globe valve coefficient
X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv
P₁ and P₂ are absolute bar and mass flow is kg/h. This is Spirax Eq. 3.21.2 normalized at zero drop, with choked flow at P₂ ≤ 0.58·P₁. Check valve noise, pressure recovery and capacity with the manufacturer.
Worked examples