45 minute batch tank warm-up

A 12,000 lb water batch must warm from 18 °C to 80 °C in 45 minutes.

Inputs

lb
min
Btu/(lb·°F)
°F
°F
%
psig
psig
Shell-and-tube steam condensation
Shell-and-tube steam condensationSTEAM FLOW 2,293.7 lb/hr. HEATING DUTY 2.14M Btu/h. VALVE Cv 12.67 Cv. TRAP LOAD 6,881.1 lb/hrSTEAM FLOW2,293.7lb/hrHEATING DUTY2.14MBtu/hVALVE Cv12.67CvTRAP LOAD6,881.1lb/hrSTEAM INCONTROL VALVEPROCESS INPROCESS OUTCONDENSATEValve P₂ / P₁ absoluteChoked · 34.61%0%58% critical ratio100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Design heating duty
2,142,310.58Btu/h
Process heating duty
1,785,258.81Btu/h
Condensing steam demand
2,293.7lb/hr
Screened trap capacity
6,881.1lb/hr
Trap capacity factor
3×
Required valve Cv
12.67Cv
Required valve Kv
10.96Kv
Valve flow regime
Choked
Valve P₂/P₁ absolute
34.61%
Condensing temperature
266.76°F
Steam latent heat
934Btu/lb
Terminal temperature approach
90.76°F

Check the original case

Halving the warm-up period doubles calculated steam demand. The batch trap screen uses 3×.

  • Condensing steam demand2,293.7 lb/hr
  • Design heating duty2,142,310.58 Btu/h
  • Required valve Cv12.67 Cv
  • Screened trap capacity6,881.1 lb/hr

Formulas and assumptions

Continuous or batch heat duty

Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes

Use mass per hour for continuous operation or an equivalent hourly batch rate. The target temperature must stay below steam saturation in the exchanger.

Steam and trap load

m_steam = Q/h_fg(P₂); m_trap = factor·m_steam

Use 2× for a continuous screen and 3× for a batch startup screen. Confirm trap capacity at the minimum differential pressure and review exchanger stall.

Globe valve coefficient

X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv

P₁ and P₂ are absolute bar and mass flow is kg/h. This is Spirax Eq. 3.21.2 normalized at zero drop, with choked flow at P₂ ≤ 0.58·P₁. Check valve noise, pressure recovery and capacity with the manufacturer.

Worked examples

Open a case to edit its inputs.