45 minute batch tank warm-up
A 12,000 lb water batch must warm from 18 °C to 80 °C in 45 minutes.
Inputs
Inputs
- Heating mode
- Batch warm-up
- Batch mass
- 12,000 lb
- Warm-up time
- 45 min
- Process fluid heat capacity
- 1 Btu/(lb·°F)
- Inlet or initial temperature
- 64.4 °F
- Outlet or target temperature
- 176 °F
- Heat loss margin
- 20 %
- Valve inlet pressure P₁
- 100 psig
- Condensing pressure P₂
- 25 psig
Calculation results
- Design heating duty
- 2,142,310.58Btu/h
- Process heating duty
- 1,785,258.81Btu/h
- Condensing steam demand
- 2,293.7lb/hr
- Screened trap capacity
- 6,881.1lb/hr
- Trap capacity factor
- 3×
- Required valve Cv
- 12.67Cv
- Required valve Kv
- 10.96Kv
- Valve flow regime
- Choked
- Valve P₂/P₁ absolute
- 34.61%
- Condensing temperature
- 266.76°F
- Steam latent heat
- 934Btu/lb
- Terminal temperature approach
- 90.76°F
Calculation basis
- Continuous or batch heat duty
Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes - Steam and trap load
m_steam = Q/h_fg(P₂); m_trap = factor·m_steam - Globe valve coefficient
X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv
Check the original case
Halving the warm-up period doubles calculated steam demand. The batch trap screen uses 3×.
- Condensing steam demand2,293.7 lb/hr
- Design heating duty2,142,310.58 Btu/h
- Required valve Cv12.67 Cv
- Screened trap capacity6,881.1 lb/hr
Formulas and assumptions
Continuous or batch heat duty
Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes
Use mass per hour for continuous operation or an equivalent hourly batch rate. The target temperature must stay below steam saturation in the exchanger.
Steam and trap load
m_steam = Q/h_fg(P₂); m_trap = factor·m_steam
Use 2× for a continuous screen and 3× for a batch startup screen. Confirm trap capacity at the minimum differential pressure and review exchanger stall.
Globe valve coefficient
X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv
P₁ and P₂ are absolute bar and mass flow is kg/h. This is Spirax Eq. 3.21.2 normalized at zero drop, with choked flow at P₂ ≤ 0.58·P₁. Check valve noise, pressure recovery and capacity with the manufacturer.
Worked examples
Open a case to edit its inputs.