Continuous process water heater

A shell-and-tube unit heats 18,000 lb/hr of process water from 22 °C to 75 °C with a 12% duty margin.

Inputs

lb/hr
Btu/(lb·°F)
°F
°F
%
psig
psig
Shell-and-tube steam condensation
Shell-and-tube steam condensationSTEAM FLOW 2,058.8 lb/hr. HEATING DUTY 1.92M Btu/h. VALVE Cv 11.38 Cv. TRAP LOAD 4,117.6 lb/hrSTEAM FLOW2,058.8lb/hrHEATING DUTY1.92MBtu/hVALVE Cv11.38CvTRAP LOAD4,117.6lb/hrSTEAM INCONTROL VALVEPROCESS INPROCESS OUTCONDENSATEValve P₂ / P₁ absoluteChoked · 34.61%0%58% critical ratio100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Design heating duty
1,922,896.51Btu/h
Process heating duty
1,716,871.88Btu/h
Condensing steam demand
2,058.8lb/hr
Screened trap capacity
4,117.6lb/hr
Trap capacity factor
2×
Required valve Cv
11.38Cv
Required valve Kv
9.84Kv
Valve flow regime
Choked
Valve P₂/P₁ absolute
34.61%
Condensing temperature
266.76°F
Steam latent heat
934Btu/lb
Terminal temperature approach
99.76°F

Check the original case

Divide the design duty by downstream latent heat. The trap screen uses twice the condensing flow.

  • Condensing steam demand2,058.8 lb/hr
  • Design heating duty1,922,896.51 Btu/h
  • Required valve Cv11.38 Cv
  • Screened trap capacity4,117.6 lb/hr

Formulas and assumptions

Continuous or batch heat duty

Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes

Use mass per hour for continuous operation or an equivalent hourly batch rate. The target temperature must stay below steam saturation in the exchanger.

Steam and trap load

m_steam = Q/h_fg(P₂); m_trap = factor·m_steam

Use 2× for a continuous screen and 3× for a batch startup screen. Confirm trap capacity at the minimum differential pressure and review exchanger stall.

Globe valve coefficient

X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv

P₁ and P₂ are absolute bar and mass flow is kg/h. This is Spirax Eq. 3.21.2 normalized at zero drop, with choked flow at P₂ ≤ 0.58·P₁. Check valve noise, pressure recovery and capacity with the manufacturer.

Worked examples

Open a case to edit its inputs.