Low heat-capacity process fluid

An industrial process stream has a measured heat capacity of 2.1 kJ/(kg·K) and a mass flow of 8,500 kg/h.

Inputs

lb/hr
Btu/(lb·°F)
°F
°F
%
psig
psig
Shell-and-tube steam condensation
Shell-and-tube steam condensationSTEAM FLOW 1,410.2 lb/hr. HEATING DUTY 1.31M Btu/h. VALVE Cv 6.84 Cv. TRAP LOAD 2,820.5 lb/hrSTEAM FLOW1,410.2lb/hrHEATING DUTY1.31MBtu/hVALVE Cv6.84CvTRAP LOAD2,820.5lb/hrSTEAM INCONTROL VALVEPROCESS INPROCESS OUTCONDENSATEValve P₂ / P₁ absoluteChoked · 35.65%0%58% critical ratio100%
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Design heating duty
1,307,464.43Btu/h
Process heating duty
1,167,378.96Btu/h
Condensing steam demand
1,410.2lb/hr
Screened trap capacity
2,820.5lb/hr
Trap capacity factor
2×
Required valve Cv
6.84Cv
Required valve Kv
5.91Kv
Valve flow regime
Choked
Valve P₂/P₁ absolute
35.65%
Condensing temperature
276.59°F
Steam latent heat
927.13Btu/lb
Terminal temperature approach
73.59°F

Check the original case

Compare with the duty at water heat capacity. The steam flow scales with process duty.

  • Condensing steam demand1,410.2 lb/hr
  • Design heating duty1,307,464.43 Btu/h
  • Required valve Cv6.84 Cv
  • Screened trap capacity2,820.5 lb/hr

Formulas and assumptions

Continuous or batch heat duty

Q = m·c_p·(T₂ − T₁)·(1 + allowance); m_batch,eq = mass·60/minutes

Use mass per hour for continuous operation or an equivalent hourly batch rate. The target temperature must stay below steam saturation in the exchanger.

Steam and trap load

m_steam = Q/h_fg(P₂); m_trap = factor·m_steam

Use 2× for a continuous screen and 3× for a batch startup screen. Confirm trap capacity at the minimum differential pressure and review exchanger stall.

Globe valve coefficient

X = min(0.42, 1 − P₂/P₁); Kv = m_steam/[12·P₁·√(X·(0.84 − X))/0.42]; Cv = 1.156·Kv

P₁ and P₂ are absolute bar and mass flow is kg/h. This is Spirax Eq. 3.21.2 normalized at zero drop, with choked flow at P₂ ≤ 0.58·P₁. Check valve noise, pressure recovery and capacity with the manufacturer.

Worked examples

Open a case to edit its inputs.