8 in header insulation retrofit
A 50 m steam header is evaluated for a 3 in insulation retrofit at 50 °F ambient.
Inputs
Inputs
- Dry saturated steam flow
- 16,000 lb/hr
- Inlet steam pressure
- 175 psig
- Nominal pipe size
- NPS 8
- Pipe schedule
- Schedule 40
- Equivalent length
- 196.85 ft
- Physical run length
- 164.04 ft
- Absolute roughness
- 0.0018 in
- Ambient temperature
- 50 °F
- Insulation thickness
- 3 in
- Insulation conductivity
- 0.0289 Btu/(h·ft·°F)
- Surface film coefficient
- 2.113 Btu/(h·ft²·°F)
Calculation results
- Required inlet steam velocity
- 1,848ft/min
- Required inlet velocity, alternate units
- 9.4m/s
- Darcy pressure drop
- 0.191psi
- Drop / inlet absolute pressure
- 0.1%
- Smallest size meeting screens
- NPS 5
- Velocity screening band
- Below band
- Actual pipe bore
- 7.981in
- Inlet vapor density
- 0.4154lb/ft³
- Reynolds number
- 795,271
- Darcy friction factor
- 0.0152
- Bare run heat loss
- 256,291.36Btu/h
- Insulated run heat loss
- 17,709.33Btu/h
- Heat loss reduction
- 238,582.03Btu/h
Calculation basis
- Flow area and speed
v = (m/3,600)·v_g / (πD_i²/4) - Babcock/Darcy pressure-drop screen
ΔP = f_D·(L_eq/D_i)·ρv²/2 - Radial heat loss
q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]
Check the original case
Compare bare and insulated heat loss, then adjust the material conductivity to test the heat-loss sensitivity.
- Required inlet steam velocity1,848 ft/min
- Darcy pressure drop0.191 psi
- Drop / inlet absolute pressure0.1 %
- Insulated run heat loss17,709.33 Btu/h
Formulas and assumptions
Flow area and speed
v = (m/3,600)·v_g / (πD_i²/4)
Bores use ASME B36.10 steel pipe dimensions. This sheet uses a 4,000–6,000 ft/min screening band (20.32–30.48 m/s). Spirax discusses a broader 25–40 m/s band and sizing by pressure drop for long runs.
Babcock/Darcy pressure-drop screen
ΔP = f_D·(L_eq/D_i)·ρv²/2
Use inlet saturated density and a vapor-viscosity fit. Darcy friction is 64/Re for laminar flow and Swamee–Jain for turbulent flow, with a transition blend. The suggested minimum size meets the upper speed and 10% absolute-pressure drop screens. Pressure drop is unavailable when the model would exhaust the inlet absolute pressure.
Radial heat loss
q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]
The bare tube uses its outside diameter and zero insulation resistance. The entered film coefficient represents convection and linearized radiation. Heat loss uses physical length.
Worked examples
Open a case to edit its inputs.