3 in Schedule 80 process branch

A short heavy-wall branch supplies 4,200 lb/hr. Use actual Schedule 80 bore for the velocity and pressure-drop result.

Inputs

lb/hr
psig
ft
ft
Used for heat loss. Equivalent length includes fittings.
in
°F
in
Btu/(h·ft·°F)
Btu/(h·ft²·°F)
Steam header hydraulics and insulation
Steam header hydraulics and insulationVELOCITY 4,924 ft/min. PRESS DROP 1.232 psi. DROP / INLET 0.88 %. INSUL. LOSS 3,614.89 Btu/hVELOCITY4,924ft/minPRESS DROP1.232psiDROP / INLET0.88%INSUL. LOSS3,614.89Btu/hINLETOUTLETNPS 3 · SCH 80BARE LOSSINSULATED30.77K Btu/h3,614.89 Btu/hSaturated steam velocity screenIn band04,000 ft/min–6,000 ft/minUpper screen
Live steam / heatCondensate / waterDischarge / loss

Calculation results

Required inlet steam velocity
4,924ft/min
Required inlet velocity, alternate units
25m/s
Darcy pressure drop
1.232psi
Drop / inlet absolute pressure
0.88%
Smallest size meeting screens
NPS 3
Velocity screening band
In band
Actual pipe bore
2.9in
Inlet vapor density
0.3099lb/ft³
Reynolds number
595,153
Darcy friction factor
0.01831
Bare run heat loss
30,766.91Btu/h
Insulated run heat loss
3,614.89Btu/h
Heat loss reduction
27,152.02Btu/h

Check the original case

Switch to Schedule 40 to see the effect of a larger internal diameter at the same nominal size.

  • Required inlet steam velocity4,924 ft/min
  • Darcy pressure drop1.232 psi
  • Drop / inlet absolute pressure0.88 %
  • Insulated run heat loss3,614.89 Btu/h

Formulas and assumptions

Flow area and speed

v = (m/3,600)·v_g / (πD_i²/4)

Bores use ASME B36.10 steel pipe dimensions. This sheet uses a 4,000–6,000 ft/min screening band (20.32–30.48 m/s). Spirax discusses a broader 25–40 m/s band and sizing by pressure drop for long runs.

Babcock/Darcy pressure-drop screen

ΔP = f_D·(L_eq/D_i)·ρv²/2

Use inlet saturated density and a vapor-viscosity fit. Darcy friction is 64/Re for laminar flow and Swamee–Jain for turbulent flow, with a transition blend. The suggested minimum size meets the upper speed and 10% absolute-pressure drop screens. Pressure drop is unavailable when the model would exhaust the inlet absolute pressure.

Radial heat loss

q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]

The bare tube uses its outside diameter and zero insulation resistance. The entered film coefficient represents convection and linearized radiation. Heat loss uses physical length.

Worked examples