16 in low-pressure steam manifold
A large heavy-wall manifold distributes low-pressure steam. Dry vapor specific volume is high at this pressure.
Inputs
Inputs
- Dry saturated steam flow
- 20,000 lb/hr
- Inlet steam pressure
- 15 psig
- Nominal pipe size
- NPS 16
- Pipe schedule
- Schedule 80
- Equivalent length
- 98.43 ft
- Physical run length
- 75.46 ft
- Absolute roughness
- 0.0018 in
- Ambient temperature
- 68 °F
- Insulation thickness
- 1.9685 in
- Insulation conductivity
- 0.0289 Btu/(h·ft·°F)
- Surface film coefficient
- 2.113 Btu/(h·ft²·°F)
Calculation results
- Required inlet steam velocity
- 4,140.2ft/min
- Required inlet velocity, alternate units
- 21m/s
- Darcy pressure drop
- 0.044psi
- Drop / inlet absolute pressure
- 0.15%
- Smallest size meeting screens
- NPS 14
- Velocity screening band
- In band
- Actual pipe bore
- 14.314in
- Inlet vapor density
- 0.072lb/ft³
- Reynolds number
- 676,305
- Darcy friction factor
- 0.0143
- Bare run heat loss
- 121,385.3Btu/h
- Insulated run heat loss
- 10,526.91Btu/h
- Heat loss reduction
- 110,858.39Btu/h
Calculation basis
- Flow area and speed
v = (m/3,600)·v_g / (πD_i²/4) - Babcock/Darcy pressure-drop screen
ΔP = f_D·(L_eq/D_i)·ρv²/2 - Radial heat loss
q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]
Check the original case
Inspect the displayed nominal size, actual bore and alternate velocity units.
- Required inlet steam velocity4,140.2 ft/min
- Darcy pressure drop0.044 psi
- Drop / inlet absolute pressure0.15 %
- Insulated run heat loss10,526.91 Btu/h
Formulas and assumptions
Flow area and speed
v = (m/3,600)·v_g / (πD_i²/4)
Bores use ASME B36.10 steel pipe dimensions. This sheet uses a 4,000–6,000 ft/min screening band (20.32–30.48 m/s). Spirax discusses a broader 25–40 m/s band and sizing by pressure drop for long runs.
Babcock/Darcy pressure-drop screen
ΔP = f_D·(L_eq/D_i)·ρv²/2
Use inlet saturated density and a vapor-viscosity fit. Darcy friction is 64/Re for laminar flow and Swamee–Jain for turbulent flow, with a transition blend. The suggested minimum size meets the upper speed and 10% absolute-pressure drop screens. Pressure drop is unavailable when the model would exhaust the inlet absolute pressure.
Radial heat loss
q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]
The bare tube uses its outside diameter and zero insulation resistance. The entered film coefficient represents convection and linearized radiation. Heat loss uses physical length.
Worked examples
Open a case to edit its inputs.