Undersized 2 in steam main

An existing two-inch main needs to transport 7,500 lb/hr at 75 psig. Screen the magnitude of the hydraulic constraint.

Inputs

lb/hr
psig
ft
ft
Used for heat loss. Equivalent length includes fittings.
in
°F
in
Btu/(h·ft·°F)
Btu/(h·ft²·°F)
Steam header hydraulics and insulation
Steam header hydraulics and insulationVELOCITY 26.35K ft/min. PRESS DROP 77.525 psi. DROP / INLET 86.43 %. INSUL. LOSS 5,248.88 Btu/hVELOCITY26.35Kft/minPRESS DROP77.525psiDROP / INLET86.43%INSUL. LOSS5,248.88Btu/hINLETOUTLETNPS 2 · SCH 40BARE LOSSINSULATED39.12K Btu/h5,248.88 Btu/hSaturated steam velocity screenAbove band04,000 ft/min–6,000 ft/minUpper screen
Live steam / heatCondensate / waterDischarge / loss

Calculation results

  • Velocity exceeds the 6,000 ft/min screening ceiling.
  • Pressure drop exceeds 10% of inlet absolute pressure. Use a compressible-flow model.
Required inlet steam velocity
26,351.8ft/min
Required inlet velocity, alternate units
133.9m/s
Darcy pressure drop
77.525psi
Drop / inlet absolute pressure
86.43%
Smallest size meeting screens
NPS 5
Velocity screening band
Above band
Actual pipe bore
2.067in
Inlet vapor density
0.2036lb/ft³
Reynolds number
1,566,368
Darcy friction factor
0.01921
Bare run heat loss
39,115.04Btu/h
Insulated run heat loss
5,248.88Btu/h
Heat loss reduction
33,866.16Btu/h

Check the original case

Use the smallest screened size as a starting point for compressible analysis when the current drop exceeds the model limit.

  • Required inlet steam velocity26,351.8 ft/min
  • Darcy pressure drop77.525 psi
  • Drop / inlet absolute pressure86.43 %
  • Insulated run heat loss5,248.88 Btu/h

Formulas and assumptions

Flow area and speed

v = (m/3,600)·v_g / (πD_i²/4)

Bores use ASME B36.10 steel pipe dimensions. This sheet uses a 4,000–6,000 ft/min screening band (20.32–30.48 m/s). Spirax discusses a broader 25–40 m/s band and sizing by pressure drop for long runs.

Babcock/Darcy pressure-drop screen

ΔP = f_D·(L_eq/D_i)·ρv²/2

Use inlet saturated density and a vapor-viscosity fit. Darcy friction is 64/Re for laminar flow and Swamee–Jain for turbulent flow, with a transition blend. The suggested minimum size meets the upper speed and 10% absolute-pressure drop screens. Pressure drop is unavailable when the model would exhaust the inlet absolute pressure.

Radial heat loss

q/L = (T_steam − T_air) / [ln(D_2/D_1)/(2πk) + 1/(πD_2h)]

The bare tube uses its outside diameter and zero insulation resistance. The entered film coefficient represents convection and linearized radiation. Heat loss uses physical length.

Worked examples

Open a case to edit its inputs.