Match the pedestal to the plate footprint. This fixes A₂/A₁ at one and isolates the unconfined J8 bearing strength.
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
ANSI/AISC 360-22J8 · DG 1
Inputs
LRFD
Use loads and strengths from the selected method. Re-enter values after switching methods.
Base plate plan
Limit exceeded
Bearing P
497.25kip
Bearing area
90.293in²
Min. plate t
1.264in
Gov. length
4.3in
The dashed rectangle is the 0.95d × 0.80b_f effective column footprint used to measure m and n.
Calculation results
Limit state
Demand
Available
Use
Concrete bearing
315 kip
497.25 kip
63.3%
Plate thickness
1.264 in
1.125 in
112.4%
Calculation values
Plate area A₁
225 in²
Similar support area A₂
225 in²
Confinement multiplier
1
Applied bearing pressure
1.4 ksi
Projection m
2.608 in
Projection n
4.3 in
Inner projection n′
2.269 in
Yield-line factor λ
0.979
Effective inner λn′
2.221 in
Nominal concrete bearing
765 kip
Available bearing · LRFD
497.25 kip
Available bearing · ASD
331.169 kip
SteelBeamLab / AISC 360-22 J8 · DG 1
Plate bearing on the full pedestal area
LRFD · US customary
For an I-shaped column in centered full-contact compression on a rectangular pedestal. Check the governing concrete code, anchors, grout, welds, and any eccentric load separately.
Entered values
Required compression Pᵣ
315 kip
Column depth d
10.3 in
Column flange width b_f
8 in
Plate length N
15 in
Plate width B
15 in
Trial thickness t
1.125 in
Steel yield stress Fᵧ
36 ksi
Pedestal length
15 in
Pedestal width
15 in
Concrete strength f′c
4 ksi
Key results
Bearing P
497.25kip
Bearing area
90.293in²
Min. plate t
1.264in
Gov. length
4.3in
Limit-state screening
Limit state
Demand
Available
Use
Concrete bearing
315 kip
497.25 kip
63.3%
Plate thickness
1.264 in
1.125 in
112.4%
Preliminary structural screening. A licensed SE/PE must review results against the complete project specifications.
Worked solution at the starting values
Use bearing area 225 in² and confinement multiplier 1.
Compare m = 2.608 in, n = 4.3 in, and λn′ = 2.221 in.
Use the governing projection to calculate the minimum plate thickness of 1.264 in.
Calculation basis
For an I-shaped column in centered full-contact compression on a rectangular pedestal. Check the governing concrete code, anchors, grout, welds, and any eccentric load separately.
Concrete confinement
J8 uses 0.85f′cA₁ times the lesser of 2 and √(A₂/A₁). Here A₂ is the largest centered rectangle similar to the plate that fits on the pedestal. Use φc = 0.65 or Ωc = 2.31. The required bearing-only area holds the plate aspect ratio and pedestal fixed.
Plate projection
DG 1 uses m = (N − 0.95d)/2, n = (B − 0.80b_f)/2, and n′ = √(db_f)/4. With X = [4db_f/(d + b_f)²](Pᵣ/available concrete bearing), λ = 2√X/(1 + √(1 − X)), capped at one. The governing projection is the largest of m, n, and λn′.
Thickness
Use tₘᵢₙ = ℓ√[2Pᵣ/(FᵧBN·factor)]. The factor is 0.90 for LRFD and 1/1.67 for ASD. Compare the theoretical minimum to the selected plate thickness and check the concrete bearing separately.