Storage and Tankless Sizing for Two Overlapping Showers

Two 2 gpm showers run for ten minutes each, starting at minutes zero and five. The heater outlet is 120°F, the winter inlet is 50°F and the two fixtures mix to 105°F.

Try it Stagger the second shower to start at minute ten. The first-hour volume stays the same, but the peak tankless flow drops.

Water temperature and usage
°F
°F
°F
US gal
Shower 1
US gal/min
min
min
Shower 2
US gal/min
min
min
Tub or sink
US gal/min
min
min
Hot-only appliance
US gal/min
min
min
Operating cost
$/kWh
$/therm
USD
Required first-hour hot volume
31.4 US gal
Tankless outlet flow at peak
3.14 US gal/min
Heat pump savings / year
384.29 USD

Compare storage FHR and tankless flow at the entered water temperature rise.

Peak draw & annual operating cost

Peak hot-water flow and modeled annual billsPeak flow 3.14 US gal/min. First-hour hot volume 31.4 US gal. Heat pump annual bill 137.03 USD. Hot outlet flow · US gal/min024015304560 minAnnual operating cost · USDElectric tank$521Gas tank$232Gas tankless$161Heat pump$137
The step chart adds overlapping hot-side fixture flows. The bars show modeled annual energy cost at the entered rates.
Required temperature rise
70 °F
Tankless delivered heating power
110,088 Btu/h
Useful water heat / year
10.228 MMBtu
Electric storage bill / year
521.32 USD
Gas storage bill / year
231.73 USD
Gas tankless bill / year
161.2 USD
Heat pump bill / year
137.03 USD
Heat pump simple payback
4 years
Download

How this calculation works

Convert mixed fixture flow to heater outlet flow with (T_mixed − T_cold) ÷ (T_hot − T_cold). The hot-only appliance uses its full entered flow. Sum hot flow × minutes to get the required first-hour hot-water volume.

Overlapping draws add together. Report the largest concurrent outlet flow at the entered temperature rise, and calculate its delivered thermal power. Compare tankless units at that flow and rise, and storage units against rated FHR at their test conditions.

Annual useful heat is 8.34 Btu per US gallon per °F × typical daily hot volume × the temperature rise × 365. Divide by the entered UEF and apply the fuel price. Use UEF ratings representative of the usage bin and installation.

This operating-cost estimate holds demand and utility rates constant. It excludes standby recirculation beyond the rating, room heat exchange, service charges, maintenance and plumbing losses.

References

Frequently asked questions

Why does shifting the showers change tankless flow but leave FHR alone?

The peak flow adds fixtures that run at the same moment. The first-hour hot volume adds all draws in the hour, regardless of overlap.

Are the two shower-head flow rates the tankless heater flow?

The heater only supplies the hot portion mixed with incoming cold water. The case uses 55/70 of each shower flow on the hot side.