Flour shaker bags

A flour handling line screens a shaker collector using a conservative design ratio.

Inputs

Collector duty
CFM
ft/min
Use 0 for the midpoint of the screening band. Enter the supplier’s design ratio when available.
Filter & housing
in
ft
Use 0 to size the online count.
ft²
FPM
Use the collector supplier’s limit for this dust.

Live results

Collector air path and media loading

Collector air path and media loadingEXHAUST FLOW3,600CFMAIR-TO-CLOTH1.999ft/minONLINE COUNT172unitsCAN VELOCITY98.5FPMDusty inletFiltered airShaker bagsCan velocityOperating air-to-clothBand 1.5 ft/min1.999 ft/minHigh 3 ft/min
Dusty air enters from the left and passes around the elements. Filtered air exits from the upper plenum.

Air-to-cloth and interstitial velocity are within the entered screening limits.

Exhaust flow
3,600 CFM
Air-to-cloth
1.99869 ft/min
Online count
172 units
Can velocity
98.5029 FPM

Media and screening band

Minimum required media
1,800 ft²
Media per element
10.472 ft²
Installed online media
1,801.18 ft²
Recommended online count
172 units
Design air-to-cloth
2 ft/min
Actual ratio in alternate units
0.609201 m/min
Screening band low
1.5 ft/min
Screening band high
3 ft/min

Can cross-section

Free can area
36.5471 ft²
Can velocity
98.5029 FPM
Entered can velocity limit
250 FPM

Worked calculation at the starting values

Dust combustibility, explosion protection and cleaning strategy require separate engineering review.

  1. Required media = 1.699011 ÷ 0.01016 = 167.2255 m².
  2. Sized online count = round up (167.2255 ÷ 0.9728784) = 172.
  3. Installed free can area = 5.574182 − 172 × π × 0.127² ÷ 4 = 3.39534 m².
Starting result snapshot
Exhaust flow
3,600 CFM
Air-to-cloth
1.99869 ft/min
Online count
172 units
Can velocity
98.5029 FPM

Equations and assumptions

Media sizing

A_min = Q ÷ (A/C)_design · N_min = ceil(A_min ÷ A_element)

A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.

Operating air-to-cloth

(A/C)_actual = Q ÷ (N_online × A_element)

CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.

Interstitial can velocity

V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)

Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.