Wood dust pulse-jet bags

A woodworking line uses pulse-jet bags at 12,000 CFM and a sized online count.

Inputs

Collector duty
CFM
ft/min
Use 0 for the midpoint of the screening band. Enter the supplier’s design ratio when available.
Filter & housing
in
ft
Use 0 to size the online count.
ft²
FPM
Use the collector supplier’s limit for this dust.

Live results

Collector air path and media loading

Collector air path and media loadingEXHAUST FLOW12,000CFMAIR-TO-CLOTH6.945ft/minONLINE COUNT110unitsCAN VELOCITY163.5FPMDusty inletFiltered airPulse jetCan velocityOperating air-to-clothBand 5 ft/min6.945 ft/minHigh 9 ft/min
Dusty air enters from the left and passes around the elements. Filtered air exits from the upper plenum.

Air-to-cloth and interstitial velocity are within the entered screening limits.

Exhaust flow
12,000 CFM
Air-to-cloth
6.94494 ft/min
Online count
110 units
Can velocity
163.484 FPM

Media and screening band

Minimum required media
1,714.29 ft²
Media per element
15.708 ft²
Installed online media
1,727.88 ft²
Recommended online count
110 units
Design air-to-cloth
7 ft/min
Actual ratio in alternate units
2.11682 m/min
Screening band low
5 ft/min
Screening band high
9 ft/min

Can cross-section

Free can area
73.4016 ft²
Can velocity
163.484 FPM
Entered can velocity limit
250 FPM

Worked calculation at the starting values

The count rounds up from required media area. The can velocity also depends on the space the installed bags take up.

  1. Required media = 5.663369 ÷ 0.03556 = 159.2624 m².
  2. Sized online count = round up (159.2624 ÷ 1.459318) = 110.
  3. Installed free can area = 8.825789 − 110 × π × 0.1524² ÷ 4 = 6.819227 m².
Starting result snapshot
Exhaust flow
12,000 CFM
Air-to-cloth
6.94494 ft/min
Online count
110 units
Can velocity
163.484 FPM

Equations and assumptions

Media sizing

A_min = Q ÷ (A/C)_design · N_min = ceil(A_min ÷ A_element)

A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.

Operating air-to-cloth

(A/C)_actual = Q ÷ (N_online × A_element)

CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.

Interstitial can velocity

V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)

Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.