Welding fume cartridges

Pleated cartridges use a stated 220 ft² of rated media per element.

Inputs

Collector duty
CFM
ft/min
Use 0 for the midpoint of the screening band. Enter the supplier’s design ratio when available.
Filter & housing
in
ft²
Use 0 to size the online count.
ft²
FPM
Use the collector supplier’s limit for this dust.

Live results

Collector air path and media loading

Collector air path and media loadingEXHAUST FLOW5,000CFMAIR-TO-CLOTH1.082ft/minONLINE COUNT21unitsCAN VELOCITY89.86FPMDusty inletFiltered airPleated mediaCan velocityOperating air-to-clothBand 0.75 ft/min1.082 ft/minHigh 1.5 ft/min
Dusty air enters from the left and passes around the elements. Filtered air exits from the upper plenum.

Air-to-cloth and interstitial velocity are within the entered screening limits.

Exhaust flow
5,000 CFM
Air-to-cloth
1.08225 ft/min
Online count
21 units
Can velocity
89.8582 FPM

Media and screening band

Minimum required media
4,444.44 ft²
Media per element
220 ft²
Installed online media
4,620 ft²
Recommended online count
21 units
Design air-to-cloth
1.125 ft/min
Actual ratio in alternate units
0.32987 m/min
Screening band low
0.75 ft/min
Screening band high
1.5 ft/min

Can cross-section

Free can area
55.6432 ft²
Can velocity
89.8582 FPM
Entered can velocity limit
180 FPM

Worked calculation at the starting values

Use the rated pleated area for filtration and the outside diameter for the can-blockage calculation.

  1. Required media = 2.359737 ÷ 0.005715 = 412.9024 m².
  2. Sized online count = round up (412.9024 ÷ 20.43867) = 21.
  3. Installed free can area = 6.967728 − 21 × π × 0.3302² ÷ 4 = 5.169423 m².
Starting result snapshot
Exhaust flow
5,000 CFM
Air-to-cloth
1.08225 ft/min
Online count
21 units
Can velocity
89.8582 FPM

Equations and assumptions

Media sizing

A_min = Q ÷ (A/C)_design · N_min = ceil(A_min ÷ A_element)

A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.

Operating air-to-cloth

(A/C)_actual = Q ÷ (N_online × A_element)

CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.

Interstitial can velocity

V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)

Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.