A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.
Operating air-to-cloth
(A/C)_actual = Q ÷ (N_online × A_element)
CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.
Interstitial can velocity
V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)
Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.
CleanroomVentLab · Calculation sheet · US customary
Welding fume cartridges
Inputs
Exhaust airflow
5,000 CFM
Collector type
Pleated cartridges
Dust material
Welding fume
Design air-to-cloth ratio
Automatic ft/min
Element diameter
13 in
Rated media per cartridge
220 ft²
Installed online count
0
Gross can cross-section
75 ft²
Maximum can velocity
180 FPM
Results
Exhaust flow
5,000 CFM
Air-to-cloth
1.08225 ft/min
Online count
21 units
Can velocity
89.8582 FPM
Minimum required media
4,444.44 ft²
Media per element
220 ft²
Installed online media
4,620 ft²
Recommended online count
21 units
Design air-to-cloth
1.125 ft/min
Actual ratio in alternate units
0.32987 m/min
Screening band low
0.75 ft/min
Screening band high
1.5 ft/min
Free can area
55.6432 ft²
Can velocity
89.8582 FPM
Entered can velocity limit
180 FPM
Air-to-cloth and interstitial velocity are within the entered screening limits.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.