CleanroomVentLab · Calculation sheet · US customary
High electricity tariff
Inputs
- Filter class
- HEPA filter
- Airflow per filter
- 1,100 CFM
- Clean pressure drop
- 0.461683 in.wg
- Current change-out limit
- 2.30841 in.wg
- Measured pressure rise
- 0.301097 in.wg/1k h
- Combined fan + motor efficiency
- 60 %
- Electricity rate
- 0.48 /kWh
- Annual operating hours
- 7,800 h
- Filter hardware
- 38
- Labor per change
- 20
- Cost display currency
- USD · US dollar
Results
- Avg. fan power
- 0.298507 kW
- Annual energy
- 1,117.61 USD
- Annual changes
- 73.7609 USD
- Economic ΔP
- 1.04274 in.wg
- Average filter pressure drop
- 1.38505 in.wg
- Extra power from loading
- 0.199005 kW
- Operating hours per filter
- 6,133.33 h
- Annual filtration energy
- 7.94467 MMBtu
- Total current annual cost
- 1,191.37 USD
- Unconstrained change-out
- 1.04274 in.wg
- Constrained change-out
- 1.04274 in.wg
- Optimal operating hours per filter
- 1,929.79 h
- Optimized annual cost
- 841.396 USD
- Modeled annual savings
- 349.975 USD
The cost curve favors a change-out below the current pressure cap.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.