Zero marginal electricity price

A sensitivity case sets the electricity rate to zero to isolate replacement economics.

Inputs

Airflow & filter loading
m³/h
Pa
Pa
Pa/1k h
Pressure rise per 1,000 operating hours at rated flow.
%
Operating & replacement cost
/kWh
h
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Filter loading and annual cost curve

Filter loading and annual cost curveAVG. FAN POWER0.1904kWANNUAL ENERGY0AUDANNUAL CHANGES476AUDECONOMIC ΔP460PaFilter loading over timeTotal annual costClean2,917 hChange-out ΔPEconomic pressure vs change-out capClean 145 Pa460 PaCap 460 Pa
The loading plot shows pressure rise across the modeled cycle. The cost curve combines energy with annualized replacement spend.

The modeled economic choice is bounded by the entered change-out cap.

Avg. fan power
0.190352 kW
Annual energy
0 AUD
Annual changes
476.023 AUD
Economic ΔP
460 Pa

Current change-out

Average filter pressure drop
302.5 Pa
Extra power from loading
0.099109 kW
Operating hours per filter
2,916.67 h
Annual filtration energy
1,484.75 kWh
Total current annual cost
476.023 AUD

Economic threshold

Unconstrained change-out
Falls with longer cycle
Constrained change-out
460 Pa
Optimal operating hours per filter
2,916.67 h
Optimized annual cost
476.023 AUD
Modeled annual savings
0 AUD

Worked calculation at the starting values

Fan energy still appears in the results. The cost model chooses the allowed pressure cap because only replacement spend varies with the threshold.

  1. Average filter pressure = (145 + 460) ÷ 2 = 302.5 Pa.
  2. Current annual total = 0 + 476.0229 = 476.0229 AUD.
  3. Modeled change-out at 460 Pa gives 476.0229 AUD per year.
Starting result snapshot
Avg. fan power
0.190352 kW
Annual energy
0 AUD
Annual changes
476.023 AUD
Economic ΔP
460 Pa

Equations and assumptions

Average filtration power

ΔP_avg = ΔP_clean + x ÷ 2 · kW = Q × ΔP_avg ÷ (1000 × η)

x is the allowed pressure rise above clean. Q is m³/s and pressure is Pa. Constant airflow, uniform loading and fixed combined efficiency are assumed.

Annualized cost

C_year = H × [kW × c + C_r × r ÷ x]

H is annual operating hours, c is price per kWh, C_r is hardware plus labor per change and r is the measured pressure rise per operating hour. Expected changes per year can be fractional.

Economic change-out pressure

x* = √(2 × C_r × r ÷ [c × Q ÷ (1000 × η)])

Add x* to the clean pressure for the unconstrained threshold. The selected economic change-out is capped by the entered pressure limit. Validate system airflow, leaks, efficiency, contamination, service life and manufacturer limits with field measurements.