ULPA high-duty filter bank

One ULPA element is evaluated at its rated flow for a continuous-duty fabrication process.

Inputs

Airflow & filter loading
m³/h
Pa
Pa
Pa/1k h
Pressure rise per 1,000 operating hours at rated flow.
%
Operating & replacement cost
/kWh
h
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Filter loading and annual cost curve

Filter loading and annual cost curveAVG. FAN POWER0.3063kWANNUAL ENERGY429.2EURANNUAL CHANGES1,060EURECONOMIC ΔP525PaFilter loading over timeTotal annual costClean2,561 hChange-out ΔPEconomic pressure vs change-out capClean 210 Pa525 PaCap 525 Pa
The loading plot shows pressure rise across the modeled cycle. The cost curve combines energy with annualized replacement spend.

The modeled economic choice is bounded by the entered change-out cap.

Avg. fan power
0.30625 kW
Annual energy
429.24 EUR
Annual changes
1,060.38 EUR
Economic ΔP
525 Pa

Current change-out

Average filter pressure drop
367.5 Pa
Extra power from loading
0.13125 kW
Operating hours per filter
2,560.98 h
Annual filtration energy
2,682.75 kWh
Total current annual cost
1,489.62 EUR

Economic threshold

Unconstrained change-out
966.274 Pa
Constrained change-out
525 Pa
Optimal operating hours per filter
2,560.98 h
Optimized annual cost
1,489.62 EUR
Modeled annual savings
0 EUR

Worked calculation at the starting values

Use the per-filter result and multiply by the number of equivalent independently loaded positions for a bank estimate.

  1. Average filter pressure = (210 + 525) ÷ 2 = 367.5 Pa.
  2. Current annual total = 429.24 + 1,060.377 = 1,489.617 EUR.
  3. Modeled change-out at 525 Pa gives 1,489.617 EUR per year.
Starting result snapshot
Avg. fan power
0.30625 kW
Annual energy
429.24 EUR
Annual changes
1,060.38 EUR
Economic ΔP
525 Pa

Equations and assumptions

Average filtration power

ΔP_avg = ΔP_clean + x ÷ 2 · kW = Q × ΔP_avg ÷ (1000 × η)

x is the allowed pressure rise above clean. Q is m³/s and pressure is Pa. Constant airflow, uniform loading and fixed combined efficiency are assumed.

Annualized cost

C_year = H × [kW × c + C_r × r ÷ x]

H is annual operating hours, c is price per kWh, C_r is hardware plus labor per change and r is the measured pressure rise per operating hour. Expected changes per year can be fractional.

Economic change-out pressure

x* = √(2 × C_r × r ÷ [c × Q ÷ (1000 × η)])

Add x* to the clean pressure for the unconstrained threshold. The selected economic change-out is capped by the entered pressure limit. Validate system airflow, leaks, efficiency, contamination, service life and manufacturer limits with field measurements.

References

More worked examples

Open calculator defaults