CleanroomVentLab · Calculation sheet · US customary
HEPA change-out baseline
Inputs
- Filter class
- HEPA filter
- Airflow per filter
- 800 CFM
- Clean pressure drop
- 0.501829 in.wg
- Current change-out limit
- 1.60585 in.wg
- Measured pressure rise
- 0.401463 in.wg/1k h
- Combined fan + motor efficiency
- 60 %
- Electricity rate
- 0.16 /kWh
- Annual operating hours
- 7,800 h
- Filter hardware
- 95
- Labor per change
- 45
- Cost display currency
- USD · US dollar
Results
- Avg. fan power
- 0.165182 kW
- Annual energy
- 206.147 USD
- Annual changes
- 397.091 USD
- Economic ΔP
- 1.60585 in.wg
- Average filter pressure drop
- 1.05384 in.wg
- Extra power from loading
- 0.0865237 kW
- Operating hours per filter
- 2,750 h
- Annual filtration energy
- 4.39626 MMBtu
- Total current annual cost
- 603.238 USD
- Unconstrained change-out
- 2.61896 in.wg
- Constrained change-out
- 1.60585 in.wg
- Optimal operating hours per filter
- 2,750 h
- Optimized annual cost
- 603.238 USD
- Modeled annual savings
- 0 USD
The modeled economic choice is bounded by the entered change-out cap.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.