High electricity tariff

An elevated tariff and lower change-out cost bring the economic minimum within the tested pressure range.

Inputs

Airflow & filter loading
CFM
in.wg
in.wg
in.wg/1k h
Pressure rise per 1,000 operating hours at rated flow.
%
Operating & replacement cost
/kWh
h
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Filter loading and annual cost curve

Filter loading and annual cost curveAVG. FAN POWER0.2985kWANNUAL ENERGY1,118USDANNUAL CHANGES73.76USDECONOMIC ΔP1.043in.wgFilter loading over timeTotal annual costClean6,133 hChange-out ΔPEconomic pressure vs change-out capClean 0.4617 in.wg1.043 in.wgCap 2.308 in.wg
The loading plot shows pressure rise across the modeled cycle. The cost curve combines energy with annualized replacement spend.

The cost curve favors a change-out below the current pressure cap.

Avg. fan power
0.298507 kW
Annual energy
1,117.61 USD
Annual changes
73.7609 USD
Economic ΔP
1.04274 in.wg

Current change-out

Average filter pressure drop
1.38505 in.wg
Extra power from loading
0.199005 kW
Operating hours per filter
6,133.33 h
Annual filtration energy
7.94467 MMBtu
Total current annual cost
1,191.37 USD

Economic threshold

Unconstrained change-out
1.04274 in.wg
Constrained change-out
1.04274 in.wg
Optimal operating hours per filter
1,929.79 h
Optimized annual cost
841.396 USD
Modeled annual savings
349.975 USD

Worked calculation at the starting values

Compare the constrained recommendation with the current limit and the savings from earlier change-out.

  1. Average filter pressure = (115 + 575) ÷ 2 = 345 Pa.
  2. Current annual total = 1,117.609 + 73.76087 = 1,191.37 USD.
  3. Modeled change-out at 259.7343 Pa gives 841.3956 USD per year.
Starting result snapshot
Avg. fan power
0.298507 kW
Annual energy
1,117.61 USD
Annual changes
73.7609 USD
Economic ΔP
1.04274 in.wg

Equations and assumptions

Average filtration power

ΔP_avg = ΔP_clean + x ÷ 2 · kW = Q × ΔP_avg ÷ (1000 × η)

x is the allowed pressure rise above clean. Q is m³/s and pressure is Pa. Constant airflow, uniform loading and fixed combined efficiency are assumed.

Annualized cost

C_year = H × [kW × c + C_r × r ÷ x]

H is annual operating hours, c is price per kWh, C_r is hardware plus labor per change and r is the measured pressure rise per operating hour. Expected changes per year can be fractional.

Economic change-out pressure

x* = √(2 × C_r × r ÷ [c × Q ÷ (1000 × η)])

Add x* to the clean pressure for the unconstrained threshold. The selected economic change-out is capped by the entered pressure limit. Validate system airflow, leaks, efficiency, contamination, service life and manufacturer limits with field measurements.

References

More worked examples