CleanroomVentLab · Calculation sheet · Metric SI
ULPA high-duty filter bank
Inputs
- Filter class
- ULPA filter
- Airflow per filter
- 1,800 m³/h
- Clean pressure drop
- 210 Pa
- Current change-out limit
- 525 Pa
- Measured pressure rise
- 123 Pa/1k h
- Combined fan + motor efficiency
- 60 %
- Electricity rate
- 0.16 /kWh
- Annual operating hours
- 8,760 h
- Filter hardware
- 220
- Labor per change
- 90
- Cost display currency
- EUR · Euro
Results
- Avg. fan power
- 0.30625 kW
- Annual energy
- 429.24 EUR
- Annual changes
- 1,060.38 EUR
- Economic ΔP
- 525 Pa
- Average filter pressure drop
- 367.5 Pa
- Extra power from loading
- 0.13125 kW
- Operating hours per filter
- 2,560.98 h
- Annual filtration energy
- 2,682.75 kWh
- Total current annual cost
- 1,489.62 EUR
- Unconstrained change-out
- 966.274 Pa
- Constrained change-out
- 525 Pa
- Optimal operating hours per filter
- 2,560.98 h
- Optimized annual cost
- 1,489.62 EUR
- Modeled annual savings
- 0 EUR
The modeled economic choice is bounded by the entered change-out cap.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.