CleanroomVentLab · Calculation sheet · Metric SI
Zero marginal electricity price
Inputs
- Filter class
- HEPA filter
- Airflow per filter
- 1,359.21 m³/h
- Clean pressure drop
- 145 Pa
- Current change-out limit
- 460 Pa
- Measured pressure rise
- 108 Pa/1k h
- Combined fan + motor efficiency
- 60 %
- Electricity rate
- 0 /kWh
- Annual operating hours
- 7,800 h
- Filter hardware
- 130
- Labor per change
- 48
- Cost display currency
- AUD · Australian dollar
Results
- Avg. fan power
- 0.190352 kW
- Annual energy
- 0 AUD
- Annual changes
- 476.023 AUD
- Economic ΔP
- 460 Pa
- Average filter pressure drop
- 302.5 Pa
- Extra power from loading
- 0.099109 kW
- Operating hours per filter
- 2,916.67 h
- Annual filtration energy
- 1,484.75 kWh
- Total current annual cost
- 476.023 AUD
- Unconstrained change-out
- Falls with longer cycle
- Constrained change-out
- 460 Pa
- Optimal operating hours per filter
- 2,916.67 h
- Optimized annual cost
- 476.023 AUD
- Modeled annual savings
- 0 AUD
The modeled economic choice is bounded by the entered change-out cap.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.
https://calcsheetlab.com/cleanroomventlab/hepa-ulpa-filter-lifecycle-cost-calculator/zero-marginal-electric-cost/