Constant-volume bypass hood

The same working and reduced positions are compared on a constant-volume bypass exhaust.

Inputs

Hood opening
ft
in
in
FPM
Control & schedule
h
Make-up air utilities
°F·h
°F·h
Decimal delivered-to-input ratio.
/kWh
/kWh
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Sash positions and annual cost

Sash positions and annual costWORKING FLOW675CFMREDUCED FLOW675CFMENERGY SAVED0MMBtuCOST SAVED0USDSash openingsMake-up air cost / yearWorking18 inReduced12 inWorking2,283 USDReduced2,283 USDReduced sash flow vs workingReduced flow675 CFMWork 675 CFM
Sash openings follow the entered heights. The bars compare annual sensible make-up air costs for the two positions.

Constant volume holds exhaust at the same flow in both sash positions.

Working flow
675 CFM
Reduced flow
675 CFM
Energy saved
0 MMBtu
Cost saved
0 USD

Airflow and face velocity

Working face velocity
90 FPM
Reduced face velocity
135 FPM
Unoccupied exhaust
675 CFM
Annual mean flow, working
675 CFM
Annual mean flow, reduced
675 CFM

Make-up air per year

Working heating input
72.9006 MMBtu
Working cooling input
6.83443 MMBtu
Working total energy
79.735 MMBtu
Reduced total energy
79.735 MMBtu
Working annual cost
2,283.39 USD
Reduced annual cost
2,283.39 USD

Worked calculation at the starting values

The model holds exhaust constant, so sash position alone produces zero conditioned air savings.

  1. Working flow = 1.524 × 0.4572 × 0.4572 = 0.3185645 m³/s.
  2. Average flow with managed sash = 0.3185645 m³/s including 0.3185645 m³/s during unoccupied hours.
  3. Sash savings = 2,283.391 − 2,283.391 = 0 USD per year.
Starting result snapshot
Working flow
675 CFM
Reduced flow
675 CFM
Energy saved
0 MMBtu
Cost saved
0 USD

Equations and assumptions

Face velocity and sash flow

Q = W × H × V_face

Use the unobstructed opening. ANSI/ASSP Z9.5 practice uses 80–100 FPM as a starting range where appropriate. Select a site-specific target after containment testing.

VAV and bypass operation

Q_reduced = max(W × H_reduced × V_face, Q_min)

VAV uses the entered minimum whenever the sash demand falls below it and during all unoccupied hours. The CAV/bypass comparison keeps working flow throughout. The same unoccupied minimum applies to both sash scenarios.

Annual sensible make-up energy

E_heat = 1.2072 × Q_mean × H_DH ÷ η · E_cool = 1.2072 × Q_mean × C_DH ÷ COP

Q_mean is the occupied/unoccupied average in m³/s. Enter degree-hours as the sum of temperature differences over hours, not HDD/CDD in degree-days. The result is purchased kWh, with an MMBtu energy-equivalent display. The model assumes similar climate-hour distribution across shifts and excludes latent loads, fans and heat recovery.

References