Heating-dominant laboratory

A metric laboratory budget has high heating degree-hours and a small cooling load.

Inputs

Hood opening
m
mm
mm
m/s
Control & schedule
%
Percent of working exhaust. Also applies as the occupied minimum.
h
Make-up air utilities
°C·h
°C·h
Decimal delivered-to-input ratio.
/kWh
/kWh
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Sash positions and annual cost

Sash positions and annual costWORKING FLOW1,094m³/hREDUCED FLOW729m³/hENERGY SAVED3,398kWhCOST SAVED276.5CADSash openingsMake-up air cost / yearWorking450 mmReduced300 mmWorking1,517 CADReduced1,241 CADReduced sash flow vs workingReduced flow729 m³/hWork 1,094 m³/h
Sash openings follow the entered heights. The bars compare annual sensible make-up air costs for the two positions.

The sash comparison uses a shared VAV minimum. Verify containment at both operating positions.

Working flow
1,093.5 m³/h
Reduced flow
729 m³/h
Energy saved
3,397.79 kWh
Cost saved
276.517 CAD

Airflow and face velocity

Working face velocity
0.45 m/s
Reduced face velocity
0.45 m/s
Unoccupied exhaust
382.725 m³/h
Annual mean flow, working
593.686 m³/h
Annual mean flow, reduced
485.501 m³/h

Make-up air per year

Working heating input
18,359.8 kWh
Working cooling input
286.181 kWh
Working total energy
18,646 kWh
Reduced total energy
15,248.2 kWh
Working annual cost
1,517.44 CAD
Reduced annual cost
1,240.92 CAD

Worked calculation at the starting values

Review the purchased heating and cooling breakdown. Enter energy tariffs for the same currency and input energy basis.

  1. Working flow = 1.5 × 0.45 × 0.45 = 0.30375 m³/s.
  2. Average flow with managed sash = 0.1348613 m³/s including 0.1063125 m³/s during unoccupied hours.
  3. Sash savings = 1,517.438 − 1,240.921 = 276.5166 CAD per year.
Starting result snapshot
Working flow
1,093.5 m³/h
Reduced flow
729 m³/h
Energy saved
3,397.79 kWh
Cost saved
276.517 CAD

Equations and assumptions

Face velocity and sash flow

Q = W × H × V_face

Use the unobstructed opening. ANSI/ASSP Z9.5 practice uses 80–100 FPM as a starting range where appropriate. Select a site-specific target after containment testing.

VAV and bypass operation

Q_reduced = max(W × H_reduced × V_face, Q_min)

VAV uses the entered minimum whenever the sash demand falls below it and during all unoccupied hours. The CAV/bypass comparison keeps working flow throughout. The same unoccupied minimum applies to both sash scenarios.

Annual sensible make-up energy

E_heat = 1.2072 × Q_mean × H_DH ÷ η · E_cool = 1.2072 × Q_mean × C_DH ÷ COP

Q_mean is the occupied/unoccupied average in m³/s. Enter degree-hours as the sum of temperature differences over hours, not HDD/CDD in degree-days. The result is purchased kWh, with an MMBtu energy-equivalent display. The model assumes similar climate-hour distribution across shifts and excludes latent loads, fans and heat recovery.

References

More worked examples

Open calculator defaults