CleanroomVentLab · Calculation sheet · Metric SI
Heating-dominant laboratory
Inputs
- Clear sash width
- 1.5 m
- Working height
- 450 mm
- Reduced height
- 300 mm
- Target face velocity
- 0.45 m/s
- Exhaust control
- Variable air volume (VAV)
- Unoccupied VAV flow
- 35 %
- Occupied hours per year
- 2,600 h
- Heating degree-hours
- 83,000 °C·h
- Cooling degree-hours
- 4,600 °C·h
- Heating efficiency
- 0.9
- Cooling COP
- 3.2
- Heating input energy rate
- 0.08 /kWh
- Cooling input energy rate
- 0.17 /kWh
- Cost display currency
- CAD · Canadian dollar
Results
- Working flow
- 1,093.5 m³/h
- Reduced flow
- 729 m³/h
- Energy saved
- 3,397.79 kWh
- Cost saved
- 276.517 CAD
- Working face velocity
- 0.45 m/s
- Reduced face velocity
- 0.45 m/s
- Unoccupied exhaust
- 382.725 m³/h
- Annual mean flow, working
- 593.686 m³/h
- Annual mean flow, reduced
- 485.501 m³/h
- Working heating input
- 18,359.8 kWh
- Working cooling input
- 286.181 kWh
- Working total energy
- 18,646 kWh
- Reduced total energy
- 15,248.2 kWh
- Working annual cost
- 1,517.44 CAD
- Reduced annual cost
- 1,240.92 CAD
The sash comparison uses a shared VAV minimum. Verify containment at both operating positions.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.