VAV with a high flow floor

The lab uses a 75% minimum VAV flow and compares working and reduced sash positions.

Inputs

Hood opening
ft
in
in
FPM
Control & schedule
%
Percent of working exhaust. Also applies as the occupied minimum.
h
Make-up air utilities
°F·h
°F·h
Decimal delivered-to-input ratio.
/kWh
/kWh
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Sash positions and annual cost

Sash positions and annual costWORKING FLOW675CFMREDUCED FLOW506.3CFMENERGY SAVED7.054MMBtuCOST SAVED202USDSash openingsMake-up air cost / yearWorking18 inReduced9 inWorking1,915 USDReduced1,713 USDReduced sash flow vs workingReduced flow506.3 CFMWork 675 CFM
Sash openings follow the entered heights. The bars compare annual sensible make-up air costs for the two positions.

The sash comparison uses a shared VAV minimum. Verify containment at both operating positions.

Working flow
675 CFM
Reduced flow
506.25 CFM
Energy saved
7.05418 MMBtu
Cost saved
202.012 USD

Airflow and face velocity

Working face velocity
90 FPM
Reduced face velocity
135 FPM
Unoccupied exhaust
506.25 CFM
Annual mean flow, working
565.967 CFM
Annual mean flow, reduced
506.25 CFM

Make-up air per year

Working heating input
61.125 MMBtu
Working cooling input
5.73047 MMBtu
Working total energy
66.8555 MMBtu
Reduced total energy
59.8013 MMBtu
Working annual cost
1,914.56 USD
Reduced annual cost
1,712.54 USD

Worked calculation at the starting values

The VAV minimum can limit the airflow reduction at the smaller sash opening.

  1. Working flow = 1.524 × 0.4572 × 0.4572 = 0.3185645 m³/s.
  2. Average flow with managed sash = 0.2389234 m³/s including 0.2389234 m³/s during unoccupied hours.
  3. Sash savings = 1,914.555 − 1,712.543 = 202.0123 USD per year.
Starting result snapshot
Working flow
675 CFM
Reduced flow
506.25 CFM
Energy saved
7.05418 MMBtu
Cost saved
202.012 USD

Equations and assumptions

Face velocity and sash flow

Q = W × H × V_face

Use the unobstructed opening. ANSI/ASSP Z9.5 practice uses 80–100 FPM as a starting range where appropriate. Select a site-specific target after containment testing.

VAV and bypass operation

Q_reduced = max(W × H_reduced × V_face, Q_min)

VAV uses the entered minimum whenever the sash demand falls below it and during all unoccupied hours. The CAV/bypass comparison keeps working flow throughout. The same unoccupied minimum applies to both sash scenarios.

Annual sensible make-up energy

E_heat = 1.2072 × Q_mean × H_DH ÷ η · E_cool = 1.2072 × Q_mean × C_DH ÷ COP

Q_mean is the occupied/unoccupied average in m³/s. Enter degree-hours as the sum of temperature differences over hours, not HDD/CDD in degree-days. The result is purchased kWh, with an MMBtu energy-equivalent display. The model assumes similar climate-hour distribution across shifts and excludes latent loads, fans and heat recovery.

References

More worked examples

Open calculator defaults