CleanroomVentLab · Calculation sheet · US customary
5-ft VAV hood, 18 in vs 12 in
Inputs
- Clear sash width
- 5 ft
- Working height
- 18 in
- Reduced height
- 12 in
- Target face velocity
- 90 FPM
- Exhaust control
- Variable air volume (VAV)
- Unoccupied VAV flow
- 35 %
- Occupied hours per year
- 2,600 h
- Heating degree-hours
- 90,000 °F·h
- Cooling degree-hours
- 30,000 °F·h
- Heating efficiency
- 0.9
- Cooling COP
- 3.2
- Heating input energy rate
- 0.09 /kWh
- Cooling input energy rate
- 0.18 /kWh
- Cost display currency
- USD · US dollar
Results
- Working flow
- 675 CFM
- Reduced flow
- 450 CFM
- Energy saved
- 7.88855 MMBtu
- Cost saved
- 225.906 USD
- Working face velocity
- 90 FPM
- Reduced face velocity
- 90 FPM
- Unoccupied exhaust
- 236.25 CFM
- Annual mean flow, working
- 366.473 CFM
- Annual mean flow, reduced
- 299.692 CFM
- Working heating input
- 39.5794 MMBtu
- Working cooling input
- 3.71057 MMBtu
- Working total energy
- 43.2899 MMBtu
- Reduced total energy
- 35.4014 MMBtu
- Working annual cost
- 1,239.7 USD
- Reduced annual cost
- 1,013.8 USD
The sash comparison uses a shared VAV minimum. Verify containment at both operating positions.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.
https://calcsheetlab.com/cleanroomventlab/laboratory-fume-hood-airflow-cost-calculator/five-foot-vav-18-vs-12/