CleanroomVentLab · Calculation sheet · Metric SI
IPA batch dryer
Inputs
- Solvent
- Isopropyl alcohol (IPA)
- Peak evaporation rate
- 10 L/h
- Process basis
- Batch · screening factor
- Batch screening factor
- 6 ×
- Process air temperature
- 80 °C
- Site elevation above sea level
- 0 m
- Temperature correction
- Estimate from temperature
- Available fresh air
- 800 Nm³/h
Results
- Min. fresh air
- 923.709 Nm³/h
- Vapor flow
- 2.94626 Nm³/h
- At avail. flow
- 19.2439 % LEL
- LEL margin
- -2.57727 pp
- Molecular weight
- 60.1 g/mol
- Liquid specific gravity
- 0.79
- Reference LEL
- 2 % vol
- Vapor mass rate
- 7.9 kg/h
- Vapor at process conditions
- 3.80916 m³/h
- Theoretical airflow at reference LEL
- 147.313 Nm³/h
- Temperature multiplier
- 1.04506 ×
- Temperature-adjusted LEL
- 1.91376 % vol
- Screening factor
- 6 ×
- Target concentration
- 16.6667 % LEL
- Concentration at calculated minimum
- 16.6667 % LEL
- Available fresh air
- 800 Nm³/h
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 1,194.24 m³/h
- Equivalent actual available air
- 1,034.3 m³/h
Available fresh air is below the modeled target. Batch results use the entered peak rate and screening factor. Review the time-dependent release and applicable batch method.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.
https://calcsheetlab.com/cleanroomventlab/nfpa-86-solvent-vapor-dilution-calculator/ipa-batch-dryer/