CleanroomVentLab · Calculation sheet · US customary
MEK continuous finishing
Inputs
- Solvent
- Methyl ethyl ketone (MEK)
- Peak evaporation rate
- 1.25 gal/h
- Process basis
- Continuous · 4× (25% LEL)
- Process air temperature
- 338 °F
- Site elevation above sea level
- 0 ft
- Temperature correction
- Enter verified multiplier
- Ventilation multiplier
- 1.18 ×
- Available fresh air
- 460 SCFM
Results
- Min. fresh air
- 249.898 SCFM
- Vapor flow
- 0.741224 SCFM
- At avail. flow
- 13.5814 % LEL
- LEL margin
- +11.4186 pp
- Molecular weight
- 72.1 g/mol
- Liquid specific gravity
- 0.81
- Reference LEL
- 1.4 % vol
- Vapor mass rate
- 8.44972 lb/h
- Vapor at process conditions
- 1.13775 ACFM
- Theoretical airflow at reference LEL
- 52.9446 SCFM
- Temperature multiplier
- 1.18 ×
- Temperature-adjusted LEL
- 1.18644 % vol
- Screening factor
- 4 ×
- Target concentration
- 25 % LEL
- Concentration at calculated minimum
- 25 % LEL
- Available fresh air
- 460 SCFM
- Estimated ambient pressure
- 101.325 kPa abs
- Minimum actual fresh air
- 383.583 ACFM
- Equivalent actual available air
- 706.079 ACFM
Available fresh air meets the modeled dilution target.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.
https://calcsheetlab.com/cleanroomventlab/nfpa-86-solvent-vapor-dilution-calculator/mek-continuous-finishing/