Facility sizing

Walk-In Cooler & Freezer Heat Load Calculator

Size a six-sided commercial cold room from insulation, door air exchanges, product pull-down, internal heat and compressor runtime.

Sized capacity
6.15kW
Refrig. tons
1.75TR
24-hour load
4.61kW
Product load
1.52kW
Edit inputs

Inputs

Edit any value to recalculate.

Room envelope

Use assembly R-values. The floor can have a different boundary temperature.

m
m
m
°C
°C
°C
m²·K/W
m²·K/W
m²·K/W
Door air exchange

One exchange replaces one room volume. Enter effective daily exchanges after door controls.

changes/day
%
%
Product cooling
kg/day
°C
°C
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
h
Internal loads & runtime

This sizing screen uses 16–20 available compressor hours per day.

kW
h/day
kW
h/day
kW
h/day
kW
h/day
%
h/day

Heat entering the walk-in

Heat entering the walk-inThe stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.Surrounding air29 °CRoom setpoint-18 °CVolume 67.2 m³Positive gains / 24-hour averagePanelsDoor airProductInternal

The stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.

Calculation breakdown

Four walls
0.58kW
Ceiling
0.22kW
Floor
0.16kW
Net panel transmission
0.97kW
Door infiltration incl. moisture
1.52kW
Product heat per day
131,261kJ
Lighting heat
0.08kW
Fan heat
0.37kW
Occupant heat
0.08kW
Retained defrost heat
0.08kW
Runtime-adjusted capacity
6.15kW
Product-window capacity
6.13kW
Inside box volume
67.2m³

Worked examples

Open a case with its assumptions loaded, then edit the inputs.

Formulas and assumptions

Panel transmission

Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]

Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.

Door infiltration

Q = V × exchanges/day × ρda × Δh / 86,400

The air-change method uses the entering dry-air density and moist-air enthalpy difference at standard atmospheric pressure. In a freezer it adds freezing heat for moisture removed from the incoming air. This is a daily screening estimate.

Product cooling and internal loads

E = m × (c₊ΔT₊ + Lf + c₋ΔT₋)

The fusion term applies to product crossing below its freezing point. Lighting, fans, occupancy and retained defrost heat are averaged over 24 hours. Respiration heat for living produce can be estimated with the produce tool and carried as an additional load in a detailed design.

Compressor sizing

Qsize = max(Qavg × 24 / runtime, Qbase + E / cooling window)

Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.

References

Questions and answers

How many air exchanges should a walk-in door represent?

Use door-use observations or an engineering estimate for the volume of air exchanged over a day. Door opening duration, dock temperature, pressure imbalance, and strip curtains can change this input substantially.

Why can the product cooling window control equipment size?

A batch arriving over a short period adds its whole thermal load within that window. Sizing only from the daily average can leave too little capacity during receiving.