Worked example · Facility sizing

Supermarket walk-in freezer

A supermarket back-room freezer receives a mix of unfrozen replenishment product and electric defrost heat.

Sized capacity
7.22kW
Refrig. tons
2.05TR
24-hour load
5.41kW
Product load
1.83kW
Edit inputs

Inputs

Edit any value to recalculate.

Room envelope

Use assembly R-values. The floor can have a different boundary temperature.

m
m
m
°C
°C
°C
m²·K/W
m²·K/W
m²·K/W
Door air exchange

One exchange replaces one room volume. Enter effective daily exchanges after door controls.

changes/day
%
%
Product cooling
kg/day
°C
°C
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
h
Internal loads & runtime

This sizing screen uses 16–20 available compressor hours per day.

kW
h/day
kW
h/day
kW
h/day
kW
h/day
%
h/day

Heat entering the walk-in

Heat entering the walk-inThe stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.Surrounding air27 °CRoom setpoint-20 °CVolume 97.5 m³Positive gains / 24-hour averagePanelsDoor airProductInternal

The stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.

Calculation breakdown

Four walls
0.72kW
Ceiling
0.29kW
Floor
0.24kW
Net panel transmission
1.25kW
Door infiltration incl. moisture
1.69kW
Product heat per day
158,113kJ
Lighting heat
0.08kW
Fan heat
0.37kW
Occupant heat
0.08kW
Retained defrost heat
0.11kW
Runtime-adjusted capacity
7.22kW
Product-window capacity
6.72kW
Inside box volume
97.5m³

Work through this case

  1. Product heat per day 158,113kJ
  2. Retained defrost heat 0.11kW
  3. Runtime-adjusted capacity 7.22kW

Compare the daily runtime allowance and the product-window capacity. Confirm product enthalpy for the actual mix of received cases.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Panel transmission

Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]

Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.

Door infiltration

Q = V × exchanges/day × ρda × Δh / 86,400

The air-change method uses the entering dry-air density and moist-air enthalpy difference at standard atmospheric pressure. In a freezer it adds freezing heat for moisture removed from the incoming air. This is a daily screening estimate.

Product cooling and internal loads

E = m × (c₊ΔT₊ + Lf + c₋ΔT₋)

The fusion term applies to product crossing below its freezing point. Lighting, fans, occupancy and retained defrost heat are averaged over 24 hours. Respiration heat for living produce can be estimated with the produce tool and carried as an additional load in a detailed design.

Compressor sizing

Qsize = max(Qavg × 24 / runtime, Qbase + E / cooling window)

Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.

References

Questions and answers

What should I check in the supermarket walk-in freezer example?

Compare the daily runtime allowance and the product-window capacity. Confirm product enthalpy for the actual mix of received cases.