Worked example · Facility sizing

Restaurant walk-in cooler

A small foodservice cooler receives a daily load of chilled ingredients, with a separate temperature boundary below the floor.

Sized capacity
1.87kW
Refrig. tons
0.53TR
24-hour load
1.4kW
Product load
0.06kW
Edit inputs

Inputs

Edit any value to recalculate.

Room envelope

Use assembly R-values. The floor can have a different boundary temperature.

m
m
m
°C
°C
°C
m²·K/W
m²·K/W
m²·K/W
Door air exchange

One exchange replaces one room volume. Enter effective daily exchanges after door controls.

changes/day
%
%
Product cooling
kg/day
°C
°C
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
h
Internal loads & runtime

This sizing screen uses 16–20 available compressor hours per day.

kW
h/day
kW
h/day
kW
h/day
kW
h/day
%
h/day

Heat entering the walk-in

Heat entering the walk-inThe stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.Surrounding air29 °CRoom setpoint3 °CVolume 21.8 m³Positive gains / 24-hour averagePanelsDoor airProductInternal

The stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.

Calculation breakdown

Four walls
0.22kW
Ceiling
0.06kW
Floor
0.03kW
Net panel transmission
0.31kW
Door infiltration incl. moisture
0.42kW
Product heat per day
5,580kJ
Lighting heat
0.08kW
Fan heat
0.37kW
Occupant heat
0.08kW
Retained defrost heat
0.08kW
Runtime-adjusted capacity
1.87kW
Product-window capacity
1.47kW
Inside box volume
21.84m³

Work through this case

  1. Door infiltration incl. moisture 0.42kW
  2. Net panel transmission 0.31kW
  3. Sized capacity 1.87kW

Compare door infiltration with the panel load before changing insulation. The product stays above its freezing point during pull-down.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Panel transmission

Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]

Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.

Door infiltration

Q = V × exchanges/day × ρda × Δh / 86,400

The air-change method uses the entering dry-air density and moist-air enthalpy difference at standard atmospheric pressure. In a freezer it adds freezing heat for moisture removed from the incoming air. This is a daily screening estimate.

Product cooling and internal loads

E = m × (c₊ΔT₊ + Lf + c₋ΔT₋)

The fusion term applies to product crossing below its freezing point. Lighting, fans, occupancy and retained defrost heat are averaged over 24 hours. Respiration heat for living produce can be estimated with the produce tool and carried as an additional load in a detailed design.

Compressor sizing

Qsize = max(Qavg × 24 / runtime, Qbase + E / cooling window)

Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.

References

Questions and answers

What should I check in the restaurant walk-in cooler example?

Compare door infiltration with the panel load before changing insulation. The product stays above its freezing point during pull-down.